Chapter 6 Specification of Parameters GK600 User Manual
- 116 -
A0-03
Parameter restoration
Range: 0~4
Factory default:
0
0: No operation
1: Clear fault record
When this parameter is set to 1, all fault record of Group U1 will be cleared.
2: Restore all parameters to factory default (excluding motor parameters)
3: Restore all parameters to factory default (including motor parameters)
4: Restore all parameters to backup parameters
A0-04
Parameter backup
Range: 0~1
Factory default:
0
0: No operation
1: Backup all parameters
A0-05
Parameter copy
Range: 0~3
Factory default:
0
0: No operation
1: Upload all parameters other than Group U to control panel
2: Download all parameters of control panel other than d0-01~d0-18 and d3-01~d3-18 to drive
3: Download all parameters of control panel to drive
A0-06
Type of drive
Range: 0~1
Factory default:
0
0: Type G (applicable to constant-torque load)
1: Type L (applicable to light-duty load)
A0-07
Power supply type of
SMPS
Range: 0~1
Factory default:
0
0: Supplied by DC bus voltage of drive main circuit
The switching power supply inside the drive is supplied by DC bus voltage.
1: Supplied independently
The switching power supply inside the drive is not supplied by DC bus voltage, while it is
supplied by independent rectifier circuit or battery, and in such circumstance, option board
EPC-VD2 is required for detecting the DC bus voltage of main circuit. This setting is usually
for occasions that the work of drive control circuit cannot be stopped at power loss.
A0-08
Motor 1 / motor 2
selection
Range: 0~1
Factory default:
0
0: Motor 1
Selects the current loaded motor as motor 1. Set the parameters of motor 1 in parameter