GK600 User Manual Chapter 6 Specification of Parameters
-
213 -
2: Cycle repeated
PLC automatically starts another cycle after finishing one cycle until there is a stop
command, shown as Fig. 6-52.
Fig. 6-52
Tens place: power loss memory
0: No memory on power loss
The drive does not memorize PLC run status on power loss and starts the run from step 0
after power up again.
1: Memorized on power loss
The drive saves PLC run status on power loss, including the run step, run frequency and
finished run time at the moment of power loss. After the next power up, the run will be
continued in accordance with the memorized status.
Hundreds place: starting mode
0: Run from the first step “multi-step frequency 0”
When restarted after stop, the drive will start to run from “step 0”.
1: Continue to run from the step of stop (or fault)
At the moment drive stop, the drive automatically records the run time of current step. When
restarted, the drive will gets into this step, continue to run the remanent time with the
frequency of this step, shown as Fig. 6-53.