Chapter 5 List of Parameters GK600 User Manual
- 100 -
Parameter
Designation
Scope
Factory
default
Attr
F2-01 Setting of multi-step 0
Ones place: FREQ setting
0: Multi-step FREQ 0 (F1-02)
1: AI1
2: AI2
3: EAI (on IO option)
4: X6/DI pulse input
5: Process PID output
6: Multi-step FREQ
7: Communication
Tens place: run direction
0: Forward
1: Reverse
2: Determined by run command
Hundreds place: Accel/Decel time
0: Accel/Decel time 1
1: Accel/Decel time 2
2: Accel/Decel time 3
3: Accel/Decel time 4
000
×
F2-02 Run time of step 0
0.0s(min)~6000.0s(min)
0.0s
△
F2-03 Setting of step 1
Ones place: FREQ setting
0: Multi-step FREQ 1 (F1-03)
1~7: Same as F2-01
Tens place: run direction (same as
F2-01)
Hundreds place: Accel/Decel time
option (same as F2-01)
000
×
F2-04 Run time of step 1
0.0s(min)~6000.0s(min)
0.0s
△
F2-05 Setting of step 2
Ones place: FREQ setting
0: Multi-step FREQ 2 (F1-04)
1~7: Same as F2-01
Tens place: run direction (same as
F2-01)
Hundreds place: Accel/Decel time
option (same as F2-01)
000
×
F2-06 Run time of step 2
0.0s(min)~6000.0s(min)
0.0s
△
F2-07 Setting of step 3
Ones place: FREQ setting
0: Multi-step FREQ 3 (F1-05)
1~7: Same as F2-01
Tens place: run direction (same as
F2-01)
Hundreds place: Accel/Decel time
option (same as F2-01)
000
×