Chapter 5 List of Parameters GK600 User Manual
- 110 -
Parameter
Designation
Scope
Factory
default
Attr
U0-11 Drive status
Ones place: run status
0: Accelerating
1: Decelerating
2: Constant speed run
Tens place: drive status
0: Stop
1: Running
2: Autotuning
00
◎
U0-12 AI1 input voltage
0.00V~10.00V
0.00V
◎
U0-13 AI2 input voltage
-10.00V~10.00V
0.00V
◎
U0-14 EAI input voltage
0.00V~10.00V
0.00V
◎
U0-15 AO1 output
0.0%~100.0%
0.0%
◎
U0-16 EAO output
0.0%~100.0%
0.0%
◎
U0-17 X6/DI HF pulse FREQ
0.0kHz~50.0kHz
0.0kHz
◎
U0-18 Digital input terminal status 00~7F
00
◎
U0-19
Digital output terminal
status
0~7
0
◎
U0-20 PID set
0.0%~100.0%
0.0%
◎
U0-21 PID feedback
0.0%~100.0%
0.0%
◎
U0-22 PID input offset
-100.0%~100.0%
0.0%
◎
U0-23 PLC step
0~15
0
◎
U0-24 V/f separated target voltage
0.0%~100.0%
0.0%
◎
U0-25
V/f separated actual output
voltage
0.0%~100.0%
0.0%
◎
U0-26 Reserved
Reserved
Reserved
◎
U0-27 Reserved
Reserved
Reserved
◎
U0-28 Reserved
Reserved
Reserved
◎
U0-29 Reserved
Reserved
Reserved
◎
U0-30 Cumulative power-up time 0h~65535h
0h
◎
U0-31 Cumulative run time
0h~65535h
0h
◎
U0-32 Heat sink temperature 1
-40.0
℃
~100.0
℃
0.0
℃
◎
U0-33 Heat sink temperature 2
-40.0
℃
~100.0
℃
0.0
℃
◎
U0-34 FAL fault source
0: No fault
1: IGBT overcurrent
2: Reserved
3: Output grounding fault
4: Output overcurrent
5: DC bus overvoltage
6: Other sources
0
◎
U0-35 Terminal count value
0~65535
0
◎
U0-36 Run command log at LoU 0~1
0
◎