Chapter 6 Specification of Parameters GK600 User Manual
- 154 -
C0-11
Filtering time of digital
input terminal
Range: 0.000s~1.000s
Factory default:
0.010s
Sets the filtering time of X1~X6 (when X6 is used as ordinary low-speed terminal), EX, AI1, AI2
and EAI (when used as digital input terminal). Interference immunity of digital input terminals
can be improved by appropriate filtering time. However, the response time of digital input
terminal will become slower when filtering time is increased.
ATTENTION:
This filtering time takes no effect on X6/DI when X6/DI terminal is used as DI high-speed
input terminal, while the filtering time of DI is determined by parameter C2-28.
C0-12
Delay time of terminal X1
Range: 0.0s~3600.0s
Factory default:
0.0s
C0-13
Delay time of terminal X2
Range: 0.0s~3600.0s
Factory default:
0.0s
The delayed response time of digital input terminals X1 and X2 is set by these two parameters.
ATTENTION:
Terminal delay time C0-12 and C0-13 can be set with filtering time C0-11 at the same time.
The drive will respond after the signals via X1 and X2 go through filtering time, and then
delay time. Terminals X3~X6 and EX have no delay
-
time function.
C0-14
Digital input terminal enabled
status setting 1
Range: 0000~1111
Factory default:
0000
Ones place: X1
0: Positive logic; ON when current flows through
1: Negative logic; ON when no current flows through
Tens place: X2 (same as X1)
Hundreds place: X3 (same as X1)
Thousands place: X4 (same as X1)
C0-15
Digital input terminal
enabled status setting 2
Range: 0000
~
1111
Factory default:
0000
Ones place: X5
0: Positive logic; ON when current flows through
1: Negative logic; ON when no current flows through
Tens place: X6 (same as X5)
Hundreds place: EX (on IO option board; same as X5)
Thousands place: reserved