GK600 User Manual
Chapter 6 Specification of Parameters
-
147 -
Set value Function
Set value Function
4
Run reverse (REV)
30
Frequency set mode shift
5
Three-wire control
31
Master frequency set switched
to digital setting b0-02
6
Run suspended
32
Auxiliary FREQ set switched to
digital setting b0-04
7
External stop
33
PID adjustment direction
8
Emergency stop
34
PID paused
9
Stop c DC brake
35
PID integration paused
10
DC brake stop
36
PID parameter switch
11
Coast to stop
37
Count input
12
Terminal UP
38
Count clear
13
Terminal DOWN
39
Length count
14
Clear UP/DOWN (including
∧
/
∨
key) adjustment
40
Length clear
15
Multi-step frequency terminal 1
41~62
Reserved
16
Multi-step frequency terminal 2
63
Simple PLC paused
17
Multi-step frequency terminal 3
64
Simple PLC disabled
18
Multi-step frequency terminal 4
65
Simple PLC stop memory clear
19
Accel/Decel time determinant 1
66
Start wobble frequency
20
Accel/Decel time determinant 2
67
Clear wobble frequency status
21
Accel/Decel disabled(ramp stop
not inclusive)
68
Run prohibited
22
External fault input
69
DC braking in run
23
Fault reset (RESET)
70
Analog input curve switching
24
Pulse input (valid only for X6/DI)
71~99
Reserved
25
Motor 1/2 switchover
0: No function
1: JOG forward
Perform jog forward through terminals. Jog frequency is set by b0-19, jog Accel time set by
b2-10, and jog Decel time set by b2-11. Refer to C0-00 for enabled conditions on initial power
up.
2: JOG reverse
Perform jog reverse through terminals. Jog FREQ is set by b0-19, jog Accel time by b2-10,
and jog Decel time by b2-11. Refer to C0-00 for enabled conditions on initial power up.
3: Forward (FWD)
Terminals control forward run of the drive. Refer to C0-00 for enabled conditions on initial