PLC
236
9836 3521 01
Example
: The below code issues an IDREAD order when the signal "Customer_Start_Signal" is set True,
waits for the string to be returned, and then starts the tightening cycle.
5.3.4
Multiple identifier variables
The following input and outputs can be used to control and monitor the Stations Multiple identifiers
function. See chapter: Advanced Station Settings for a description on how it is configured and works.
Inputs:
Variable
Type
Use
IDTYPE_1_STR ...
IDTYPE_6_STR
STRING(40)
The value of the last accepted string for the respective Identifier
Type. Cleared when on a positive edge of START.
IDTYPE_1_CODE
INT
Code generated by the Conversion table defined for Identifier Type 1.
IDTYPE_WO_STATE
BYTE
Work Order State. A number between 0 and 4 indicating the latest
accepted item in the Work Order list.
One (1) means that the first Work Order condition is met, two (2) that
the second one was accepted, and so on.
Set zero (0) when the Work Order sequence is reset.
IDTYPE_WO_COMPL
BOOL
Work Order Complete. Set True when all Types of the Work Order
are accepted. Set False when a cycle is started or if the Work Order
sequence is restarted.
IDTYPE_1_STS...
IDTYPE_6_STS
INT
Status of the read operation of the ID device used as source for the
respective Identifier Type:
0: Idle and OK
1: Idle and NOK
2: Busy
– waiting for the device to respond
After issuing an IDTYPE_x_RD you should wait one PLC scan before
evaluating IDTYPE_x_STS.
Summary of Contents for PowerMACS 4000
Page 2: ......
Page 46: ...System Architecture 46 9836 3521 01...
Page 267: ...Tightening 9836 3521 01 267...
Page 400: ...Tightening 400 9836 3521 01...
Page 486: ...Peripheral Devices 486 9836 3521 01...
Page 622: ...Peripheral Devices 622 9836 3521 01...
Page 664: ...References 664 9836 3521 01...
Page 668: ...9836 3521 01 2010 11 Edition 10 3 0 www atlascopco com...