PLC
242
9836 3521 01
Variable
Type
Use
PLUS_DOKUENABLE
BOOL
Set high to send Cycle data to PLUS.
If the signal is high when a new Cycle data is produced it will be
sent immediately to PLUS.
If the signal is low when a new Cycle data is produced the new
data will be stored in the Cycle data queue for the PLUS device.
When the signal goes high the whole cycle data queue will be
sent to PLUS.
PLUS_DOKUENABLE is only used if “Send cycle data
automatically” is not checked in the PLUS device in ToolsTalk
PowerMACS. If “Send cycle data automatically” is checked all
new cycle data will be sent as soon as the cycle has ended.
PLUS_QO
INT
The value of PLUS_QO will be used as station identification QO
when sending requests for TMU to PLUS.
PLUS_QO will only be used if “Use QO from PLC” is checked in
the PLUS device; otherwise the value written in “QO for request
of TMU” in the PLUS device will be used instead.
When sending cycle data to PLUS t
he value in “Station QO” in
the result will be used as QO.
PLUS_DELETE
BOOL
On a positive edge the latest cycle data is removed from the
Cycle data queue for the PLUS device used for the station.
PLUS_DROP
BOOL
If PLUS_DROP is high when cycle data is stored for a cycle no
data is written in the Cycle data queue for the PLUS device.
The PLC variable CYCLEDATASTORED can be used to know
when the data has been stored.
PLUS_FLUSH
BOOL
On a positive edge the whole cycle data queue for the PLUS
device is deleted.
PLUS_RESETSENDDATA_NOK
BOOL
On a positive edge the variable PLUS_SENDDATA_NOK is set
to FALSE.
PLUS_SEND_SONL
BOOL
On a positive edge the telegram SONL is sent to PLUS.
PLUS_SEND_SOFF
BOOL
On a positive edge the telegram SOFF is sent to PLUS.
PLUS_MANUALMODE
BOOL
Set to TRUE to tell the TC that the station is operating in manual
mode. In manual mode the TC sends NNOT as answer to every
telegram received from PLUS. No cycle data is sent to PLUS
when PLUS_MANUALMODE is high.
Only used if the station type is VBA.
PLUS_OVERRIDETMU
STRING
(25)
String that will be sent to the conversion table in the PLUS
device to get a mode number. The resulting mode number is
found in PLUS_MODE.
The string in PLUS_OVERRIDETMU will only be used if
“PowerMACS requests TMU” on the PLUS device is unchecked.
Otherwise the TMU received from PLUS will be used.
Summary of Contents for PowerMACS 4000
Page 2: ......
Page 46: ...System Architecture 46 9836 3521 01...
Page 267: ...Tightening 9836 3521 01 267...
Page 400: ...Tightening 400 9836 3521 01...
Page 486: ...Peripheral Devices 486 9836 3521 01...
Page 622: ...Peripheral Devices 622 9836 3521 01...
Page 664: ...References 664 9836 3521 01...
Page 668: ...9836 3521 01 2010 11 Edition 10 3 0 www atlascopco com...