Peripheral Devices
492
9836 3521 01
the SHARED driver to correctly map the total sizes of the respective input and output data areas defined
in the first step.
The addresses for inputs and outputs starts at 30000 and are logical only. Signals added here must also
have the prefixes “SI_” or “SO_” to be able to map to fieldbus and I/O devices.
Note!
All numerical values are written and read as Big Endian values, commonly referred to as Motorola
format.
When the variables are declared you are free to refer them from any POU (Program Organization Unit)
you have, or will, declare in the PLC project.
After mapping the input and outputs variables the next step is to configure the SHARED driver to copy the
input and output data from the fieldbus to the PLC and vice versa. This is done using the I/O Configuration
dialogue which is invoked by double-clicking on the icon for IO_Configuration worksheet of station that has
the fieldbus interface mounted.
Summary of Contents for PowerMACS 4000
Page 2: ......
Page 46: ...System Architecture 46 9836 3521 01...
Page 267: ...Tightening 9836 3521 01 267...
Page 400: ...Tightening 400 9836 3521 01...
Page 486: ...Peripheral Devices 486 9836 3521 01...
Page 622: ...Peripheral Devices 622 9836 3521 01...
Page 664: ...References 664 9836 3521 01...
Page 668: ...9836 3521 01 2010 11 Edition 10 3 0 www atlascopco com...