Tightening
274
9836 3521 01
6.5.2.1 DT - Run until Dyna-Tork
TM
Step type Id:
1
Parameters
: T (Torque), TI1 (Time1), TI2 (Time2), PERC (Current percentage), DIR (Direction).
Function
:
Run spindle, in DIR direction, until torque is T using current control. When the target is
reached a new torque, DT, is calculated as
DT = T * PERC / 100
The torque DT is then retained during the next TI1 + TI2 seconds using current control.
The PERC parameter makes it is possible to Dyna-Tork
TM
at a lower level than the target.
Before the step is started both torques, T and DT, are converted to corresponding motor
currents using the spindle parameters
T/C Factor, T/C Correction Factor
and
Gear ratio
.
When the step starts the current that corresponds to T is set as current reference to the
motor servo. When the servo reaches this current the step immediately switches the current
reference to the current that corresponds to DT which then is maintained for TI1 + TI2
seconds.
Note:
To avoid overheating of the spindle it is strongly recommended to never run Dyna-
Tork
TM
to more than 40% of the maximum torque of the spindle.
Diagram
:
Time
Torque
TI1
TI2
T
Torque
TI1
DynaTork Time 1
PERC
Percent of T
TI2
DynaTork Time 2
DT
Torque level retained during TI1 and TI2
T
Step
DT
(PERC = 100%)
DT
(PERC = 80%)
Summary of Contents for PowerMACS 4000
Page 2: ......
Page 46: ...System Architecture 46 9836 3521 01...
Page 267: ...Tightening 9836 3521 01 267...
Page 400: ...Tightening 400 9836 3521 01...
Page 486: ...Peripheral Devices 486 9836 3521 01...
Page 622: ...Peripheral Devices 622 9836 3521 01...
Page 664: ...References 664 9836 3521 01...
Page 668: ...9836 3521 01 2010 11 Edition 10 3 0 www atlascopco com...