Actual signals and parameters
216
95 HARDWARE SPECIF
Fan speed control, sine filter application etc.
95.01
FAN SPD CTRL
MODE
Selects the speed control of the optional inverter cooling fan.
CONST 50 Hz
Fan is running at constant frequency of 50 Hz when powered.
0
RUN/STOP
Drive stopped: Fan is running at constant frequency of 10 Hz.
Drive running: Fan is running at constant frequency of 50 Hz.
1
CONTROLLED
The speed of the fan is determined from IGBT temperature vs. fan speed
curve.
2
95.02
FUSE SWITCH CTRL Activates the inverter DC switch (switch fuse) monitoring function. The
monitoring must be active when the Switch Fuse Control Board (ASFC) is in
use and connected to the inverter AINT board, that is in all frame R8i inverters
equipped with the DC switch. The function must be inactive in units that do not
use the ASFC board with the DC switch, that is for frame R2i…R7i inverters
and all single drive units where no DC switch exists. The default setting (ON or
OFF) for each unit is set accordingly at the factory as default.
ACS800 IGBT pulses are always blocked when the program detects that the
DC switch is opened or inverter charging is ongoing (at power switch on). The
application program generates alarm INV DISABLED if the DC switch is
opened when the inverter is stopped. The inverter trips to fault INV DISABLED
if the DC switch is opened when the inverter is running.
OFF
Inactive
0
ON
Active
1
95.03
INT CONFIG USER
Number of parallel connected inverter modules. Activates the Reduced run
function. See section
on page
1...12
Number of parallel connected inverter modules
95.04
EX/SIN REQUEST
Activates the sine filter or Ex-motor application.
NO
Inactive
1
EX
Ex-motor application. Used with motors which comply with the ATEX directive. 2
SIN
Sine filter application. See
Sine Filters User’s Manual for ACS800 Drives
[3AFE68389178 (English)].
3
EX&SIN
EX-motor and sine filter applications. See
Sine Filters User’s Manual for
ACS800 Drives
[3AFE68389178 (English)].
4
95.05
ENA INC SW FREQ
Activates the minimum switching frequency limitation for Ex-motor
applications. Parameter is visible if parameter
EX/SIN REQUEST is set
to EX.
NO
Inactive
0
YES
Active. Minimum switching frequency limit is set to 2 kHz. Used with motors
with an ATEX certification based on 2 kHz minimum switching frequency.
1
Index
Name/Selection
Description
FbEq
Summary of Contents for ACS 800 Series
Page 1: ...ACS800 Firmware Manual Crane Control Program N697 ...
Page 4: ......
Page 26: ...Start up and control through the I O interface 26 ...
Page 36: ...Quick start up guide 36 ...
Page 52: ...Control panel 52 ...
Page 105: ...Program features 105 Figure Control diagram for Shaft synchronisation executed in 20 ms ...
Page 128: ...Program features 128 ...
Page 150: ...Application macros control location EXT1 EXT2 150 ...
Page 228: ...Actual signals and parameters 228 ...
Page 299: ...Adaptive Programming examples for crane control 299 ...
Page 305: ...Adaptive Programming examples for crane control 305 ...
Page 318: ...Analogue Extension Module 318 ...
Page 332: ...Additional data actual signals and parameters 332 ...
Page 334: ...DriveWindow 334 ...
Page 335: ...Control block diagrams 335 Control block diagrams ...
Page 336: ...Control block diagrams 336 ...
Page 337: ...Control block diagrams 337 ...
Page 338: ...Control block diagrams 338 ...
Page 340: ...www abb com drives www abb com drivespartners Contact us 3AFE68775230 Rev E EN 2012 09 25 ...