Actual signals and parameters
223
98.12
AI/O MOTOR TEMP
Activates the communication to the analogue I/O extension module and
reserves the module for the use of the motor temperature measurement
function. The parameter also defines the type and connection interface of the
module.
For more information on the temperature measurement function, see
parameter group 35 MOT TEMP MEAS.
The use of the analogue inputs (AI) and outputs (AO) of the module is shown in
the table below.
Before setting the drive parameters, ensure the module hardware settings are
appropriate for the motor temperature measurement:
1. The module node number is 9.
2. The input signal type selections are the following:
- for one Pt 100 sensor measurement, set the range to 0 … 2 V.
- for two to three Pt 100 sensors or one to three PTC sensors, set the range to
0 … 10 V.
3. The operation mode selection is unipolar.
NO
Inactive
1
RAIO-SLOT1
Communication active. Module type: RAIO. Connection interface: Option Slot 1
of the drive.
Note:
Make the module hardware settings as described above. The node
number is not required. For directions, see
RAIO Module User’s Manual
[3AFE64484567 (English)].
2
RAIO-SLOT2
Communication active. Module type: RAIO. Connection interface: Option Slot 2
of the drive.
Note:
Make the module hardware settings as described above. The node
number is not required. For directions, see
RAIO Module User’s Manual
[3AFE64484567 (English)].
3
RAIO-DDCS
Communication active. Module type: RAIO. Connection interface: Optional I/O
module adapter (AIMA) that communicates with the drive through a fibre optic
DDCS link.
Note:
Set the module node number to 9. For directions, see
RAIO Module
User’s Manual
[3AFE64484567 (English)].
4
Index
Name/Selection
Description
FbEq
Motor 1 temperature measurement
AO1
Feeds a constant current to motor 1 temperature sensor. The current
value depends on the setting of parameter
:
- AO1 is 9.1 mA with selection
- AO1 is 1.6 mA with selection
AI1
Measures voltage over motor 1 temperature sensor.
Motor 2 temperature measurement
AO2
Feeds a constant current to motor 2 temperature sensor. The current
value depends on the setting of parameter
:
- AO2 is 9.1 mA with selection
- AO2 is 1.6 mA with selection
AI2
Measures voltage over motor 2 temperature sensor.
Summary of Contents for ACS 800 Series
Page 1: ...ACS800 Firmware Manual Crane Control Program N697 ...
Page 4: ......
Page 26: ...Start up and control through the I O interface 26 ...
Page 36: ...Quick start up guide 36 ...
Page 52: ...Control panel 52 ...
Page 105: ...Program features 105 Figure Control diagram for Shaft synchronisation executed in 20 ms ...
Page 128: ...Program features 128 ...
Page 150: ...Application macros control location EXT1 EXT2 150 ...
Page 228: ...Actual signals and parameters 228 ...
Page 299: ...Adaptive Programming examples for crane control 299 ...
Page 305: ...Adaptive Programming examples for crane control 305 ...
Page 318: ...Analogue Extension Module 318 ...
Page 332: ...Additional data actual signals and parameters 332 ...
Page 334: ...DriveWindow 334 ...
Page 335: ...Control block diagrams 335 Control block diagrams ...
Page 336: ...Control block diagrams 336 ...
Page 337: ...Control block diagrams 337 ...
Page 338: ...Control block diagrams 338 ...
Page 340: ...www abb com drives www abb com drivespartners Contact us 3AFE68775230 Rev E EN 2012 09 25 ...