Fieldbus control
254
Start/Stop sequence using communication bits
This section describes the sequence of the 03.01 MAIN CONTROL WORD bits used
for starting, stopping and restarting after a fault condition or an abnormal stop, when
the drive is configured in the ABB Drives communication profile. For the flow
sequence of the communication bits, see
Flow chart for Main Control Command Bit
on page
Normal starting sequence
You can start the drive through the controlling device by giving the following main
command word bit sequence:
• Enable Bit 10 (Bit 10 = 1) to activate the fieldbus command.
• Enable Bit 4, Bit 5 and Bit 6 (Bit 4, Bit 5 and Bit 6 = 1) to activate the normal ramp
block functions.
• Enable Bit 1 (Bit 1 = 1) to deactivate the OFF2 command.
• Enable Bit 2 (Bit 2 = 1) to deactivate the OFF3 command.
• Enable Bit 0 (Bit 0 = 1) to deactivate the OFF1 command.
• Enable Bit 3 (Bit 3 = 1) to issue the start command.
Normal stopping sequence and restarting
You can stop and restart the drive through the controlling device by giving the
following main command word bit sequence:
• Disable Bit 3 (Bit 3 = 1 -> 0) to issue a stop command. Brake control must be
activated, or else the drive will stop by coasting.
• Enable Bit 3 (Bit 3 = 0 -> 1) to issue the start command.
OFF1, OFF2, OFF3 stopping sequence and restarting
You can stop and restart the drive through the controlling device by giving the
following main command word bit sequence:
• Disable Bit 0 (Bit 0 = 1 -> 0) to issue an OFF1 stop command, disable Bit 1
(Bit 1 = 1 -> 0) to issue an OFF2 stop command and Disable Bit 2 (Bit 2 = 1 -> 0)
to issue an OFF3 stop command, respectively.
• The drive can be started again only after the drive has stopped.
• To issue a start command again, disable Bit 3 (Bit 3 = 1 -> 0).
• Disable Bit 0 (Bit 0 = 1 -> 0) if the OFF2/OFF3 command was issued.
• Enable Bit 0 (Bit 0 = 0 -> 1) again if the OFF1 stop command was issued, or Bit 1
(Bit 1 = 0 -> 1) if the OFF2 stop command was issued, or Bit 2 (Bit 2 = 0 -> 1) if
the OFF3 stop command was issued.
• Enable Bit 0 (Bit 0 = 1) to make the drive ready to start.
• Enable Bit 3 (Bit 3 = 1) to issue the start command.
Summary of Contents for ACS 800 Series
Page 1: ...ACS800 Firmware Manual Crane Control Program N697 ...
Page 4: ......
Page 26: ...Start up and control through the I O interface 26 ...
Page 36: ...Quick start up guide 36 ...
Page 52: ...Control panel 52 ...
Page 105: ...Program features 105 Figure Control diagram for Shaft synchronisation executed in 20 ms ...
Page 128: ...Program features 128 ...
Page 150: ...Application macros control location EXT1 EXT2 150 ...
Page 228: ...Actual signals and parameters 228 ...
Page 299: ...Adaptive Programming examples for crane control 299 ...
Page 305: ...Adaptive Programming examples for crane control 305 ...
Page 318: ...Analogue Extension Module 318 ...
Page 332: ...Additional data actual signals and parameters 332 ...
Page 334: ...DriveWindow 334 ...
Page 335: ...Control block diagrams 335 Control block diagrams ...
Page 336: ...Control block diagrams 336 ...
Page 337: ...Control block diagrams 337 ...
Page 338: ...Control block diagrams 338 ...
Page 340: ...www abb com drives www abb com drivespartners Contact us 3AFE68775230 Rev E EN 2012 09 25 ...