Control panel
46
How to adjust a source selection (pointer) parameter
Most parameters define values that are used directly in the drive control program.
Source selection (pointer) parameters are exceptions: They point to the value of
another parameter. The parameter setting procedure differs somewhat from that of
the other parameters.
1)
Note:
Instead of pointing to another parameter, it is also possible to define a
constant with the source selection parameter. Proceed as follows:
- Change the inversion field to C. The appearance of the row changes. The rest of
the line is now a constant setting field.
- Give the constant value to the constant setting field.
- Press Enter to accept.
Step
Action
Press Key
Display
1.
See the table above to
- enter the Parameter Mode
- select the correct parameter group and parameter
- enter the parameter setting mode
1 L
->
1242.0 rpm O
84 ADAPTIVE PROGRAM
06 INPUT1
[±000.000.00]
2.
To scroll between the inversion, group, index and bit
fields.
1)
1 L
->
1242.0 rpm O
84 ADAPTIVE PROGRAM
06 INPUT1
[±000.000.00]
3.
To adjust the value of a field.
1 L
->
1242.0 rpm O
84 ADAPTIVE PROGRAM
06 INPUT1
[±000.018.00]
4.
To accept the value.
PAR
ENTER
ENTER
1 L
->
1242.0 rpm O
84 ADAPTIVE PROGRAM
06 INPUT1
[±001.018.00]
Inversion field
Group field
Index field
Bit field
Inversion field
inverts the selected parameter
value. Plus sign (+): no inversion, minus (-) sign:
inversion.
Bit field
selects the bit number (relevant only if the
parameter value is a packed boolean word).
Index field
selects the parameter index.
Group field
selects the parameter group.
Summary of Contents for ACS 800 Series
Page 1: ...ACS800 Firmware Manual Crane Control Program N697 ...
Page 4: ......
Page 26: ...Start up and control through the I O interface 26 ...
Page 36: ...Quick start up guide 36 ...
Page 52: ...Control panel 52 ...
Page 105: ...Program features 105 Figure Control diagram for Shaft synchronisation executed in 20 ms ...
Page 128: ...Program features 128 ...
Page 150: ...Application macros control location EXT1 EXT2 150 ...
Page 228: ...Actual signals and parameters 228 ...
Page 299: ...Adaptive Programming examples for crane control 299 ...
Page 305: ...Adaptive Programming examples for crane control 305 ...
Page 318: ...Analogue Extension Module 318 ...
Page 332: ...Additional data actual signals and parameters 332 ...
Page 334: ...DriveWindow 334 ...
Page 335: ...Control block diagrams 335 Control block diagrams ...
Page 336: ...Control block diagrams 336 ...
Page 337: ...Control block diagrams 337 ...
Page 338: ...Control block diagrams 338 ...
Page 340: ...www abb com drives www abb com drivespartners Contact us 3AFE68775230 Rev E EN 2012 09 25 ...