Actual signals and parameters
192
30.16
MOTOR PHASE
LOSS
Activates the Motor phase loss supervision function.
NO
Inactive
0
FAULT
Active. The drive trips on a fault.
65535
30.17
EARTH FAULT
Selects how the drive reacts when an earth fault is detected in the motor or the
motor cable. See section
on page
WARNING
The drive generates a warning.
0
FAULT
The drive trips on a fault.
65535
30.18
COMM FLT FUNC
Selects how the drive reacts in a fieldbus communication break, that is when
the drive fails to receive the Main Reference Data Set or the Auxiliary
Reference Data Set. The time delays are given with parameters
and
FAULT
Protection is active. The drive trips on a fault and stops the motor as defined
with parameter
1
NO
Protection is inactive.
2
30.19
MAIN REF DS T-OUT Defines the time delay for the Main Reference data set supervision. See
parameter
0.1 … 60.0 s
Time delay
10 … 6000
30.21
AUX DS T-OUT
Defines the delay time for the Auxiliary Reference data set supervision. See
parameter
. The drive automatically activates the supervision 60 seconds
after power switch-on if the value is other than zero.
Note:
The supervision can be displayed by setting the value to 0.
0.0 … 60.0 s
Time delay. 0.0 s = The function is inactive.
0 … 6000
30.22
IO CONFIG FUNC
Selects how the drive reacts in case an optional input or output channel has
been selected as a signal interface, but the communication to the appropriate
analogue or digital I/O extension module has not been set up accordingly in
parameter group
.
Example:
The supervision function wakes up if parameter
is set to DI7,
but
is set to NO.
NO
Inactive.
1
WARNING
Active. The drive generates a warning.
2
30.23
LIMIT WARNING
Activates/deactivates limit alarms INV CUR LIM, DC BUS LIM, MOT CUR LIM,
MOT TORQ LIM and/or MOT POW LIM. For more information, see chapter
.
0...255
Value in decimal. As default none of the alarms are active, that is, the
parameter value is 0.
bit 0 INV_CUR_LIM_IND
bit 1 DC_VOLT_LIM_IND
bit 2 MOT_CUR_LIM_IND
bit 3 MOT_TORQ_LIM_IND
bit 4 MOT_POW_LIM_IND
Example:
When parameter value is set to 3 (bit 0 and 1 values are 1), alarms
INV CUR LIM and DC BUS LIM are active.
-
30.24
EXT FAULT PTR
Defines the source or constant for selection PAR 30.24 of parameter
-255.255.31 …
+255.255.31 / C.-
32768 … C.32767
Parameter index or a constant value. See parameter
for information on
the difference.
-
Index
Name/Selection
Description
FbEq
Summary of Contents for ACS 800 Series
Page 1: ...ACS800 Firmware Manual Crane Control Program N697 ...
Page 4: ......
Page 26: ...Start up and control through the I O interface 26 ...
Page 36: ...Quick start up guide 36 ...
Page 52: ...Control panel 52 ...
Page 105: ...Program features 105 Figure Control diagram for Shaft synchronisation executed in 20 ms ...
Page 128: ...Program features 128 ...
Page 150: ...Application macros control location EXT1 EXT2 150 ...
Page 228: ...Actual signals and parameters 228 ...
Page 299: ...Adaptive Programming examples for crane control 299 ...
Page 305: ...Adaptive Programming examples for crane control 305 ...
Page 318: ...Analogue Extension Module 318 ...
Page 332: ...Additional data actual signals and parameters 332 ...
Page 334: ...DriveWindow 334 ...
Page 335: ...Control block diagrams 335 Control block diagrams ...
Page 336: ...Control block diagrams 336 ...
Page 337: ...Control block diagrams 337 ...
Page 338: ...Control block diagrams 338 ...
Page 340: ...www abb com drives www abb com drivespartners Contact us 3AFE68775230 Rev E EN 2012 09 25 ...