Actual signals and parameters
158
10.04
EXT1 STRT PTR
Defines the source or constant for value Par.
EXT1 STRT PTR of
parameter
EXT1 STRT/STP/DIR.
-255.255.31 …
+255.255.31 / C.-
32768 … C.32767
Parameter index or a constant value:
- Parameter pointer: Inversion, group, index and bit fields. The bit number is
effective only for blocks handling boolean inputs.
- Constant value: Inversion and constant fields. Inversion field must have value
C to enable the constant setting.
-
10.05
EXT2 STRT PTR
Defines the source or constant for value Par. 10.05 of parameter
EXT2
STRT/STP/DIR.
-255.255.31 …
+255.255.31 / C.-
32768 … C.32767
Parameter index or a constant value. See parameter
EXT1 STRT PTR
for information on the difference.
-
10.07
NET CONTROL
When active, fieldbus overrides the selection of parameter
EXT1 STRT/
STP/DIR. Fieldbus Control Word (except bit 11) is enabled when EXT1 is
selected as the active control location.
Note:
Only visible with the Generic Drive communication profile selected
(
).
Note:
The setting is not saved in the permanent memory (will reset to zero
when power is switched off).
0
Inactive
0
1
Active
1
10.08
NET REFERENCE
When active, fieldbus overrides the selection of parameter
EXT REF1
SELECT. Fieldbus reference REF1 is enabled when EXT1 is selected as the
active control location.
Note:
Only visible with the Generic Drive communication profile selected
(
).
Note:
The setting is not saved in the permanent memory (will reset to zero
when power is switched off).
0
Inactive
0
1
Active
1
10.09
SLOW DOWN INPUT Defines the input for the Slowdown command for external control location 1
(EXT1) and 2 (EXT2). When the command is active, the drive limits the speed
to the slowdown reference defined with parameter
SLOW DOWN REF.
NOT SEL
No Slowdown selection.
1
DI3 F,DI4 R
Slowdown command through digital input 3 and digital input 4. Slowdown
active in forward direction (UP) when DI3 = 0, inactive when DI3 = 1.
Slowdown active in reverse (down) direction when DI4 = 0, inactive when
DI4 = 1.
2
DI4 F,DI5 R
Slowdown command through digital input 4 and digital input 5.
See DI3 F,DI4 R selection.
3
DI7 F,DI8 R
Slowdown command through digital input 7 and digital input 8.
See DI3 F,DI4 R selection.
4
DI9 F,DI10 R
Slowdown command through digital input 9 and digital input 10.
See DI3 F,DI4 R selection.
5
PAR 10.19
Slowdown command through parameter
. This selection can be used if
only one DI is used for up and down directions in parallel. Slowdown active
when pointer value = 0, inactive when pointer value = 1.
6
Index
Name/Selection
Description
FbEq
Summary of Contents for ACS 800 Series
Page 1: ...ACS800 Firmware Manual Crane Control Program N697 ...
Page 4: ......
Page 26: ...Start up and control through the I O interface 26 ...
Page 36: ...Quick start up guide 36 ...
Page 52: ...Control panel 52 ...
Page 105: ...Program features 105 Figure Control diagram for Shaft synchronisation executed in 20 ms ...
Page 128: ...Program features 128 ...
Page 150: ...Application macros control location EXT1 EXT2 150 ...
Page 228: ...Actual signals and parameters 228 ...
Page 299: ...Adaptive Programming examples for crane control 299 ...
Page 305: ...Adaptive Programming examples for crane control 305 ...
Page 318: ...Analogue Extension Module 318 ...
Page 332: ...Additional data actual signals and parameters 332 ...
Page 334: ...DriveWindow 334 ...
Page 335: ...Control block diagrams 335 Control block diagrams ...
Page 336: ...Control block diagrams 336 ...
Page 337: ...Control block diagrams 337 ...
Page 338: ...Control block diagrams 338 ...
Page 340: ...www abb com drives www abb com drivespartners Contact us 3AFE68775230 Rev E EN 2012 09 25 ...