Actual signals and parameters
220
See
97.18
PWRON STRTINT
PTR
PowerON start interlock pointer. Power ON start interlock pointer can be
programmed for another use. Default: DI_IL (+.001.017.06) (start interlock
input on the RMIO board).
If you need to use DIL input for some other purpose than Power ON
acknowledge, set parameter 97.18 to 0 (= +.000.000.00) to disable Power ON
acknowledge.
-255.255.31 …
+255.255.31 / C.-
32768 … C.32767
Parameter index or a constant value.
97.19
SYNC ERR BLK LVL
Blocking level of speed correction signal
SPEED CORR BUFF in
millimetres. The default value is 0.
If the change in signal
SYNC POS ERROR is bigger than the value of
97.19 SYNC ERR BLK LVL, signal
SPEED CORR BUFF is blocked and
no synchronisation correction is performed during that period.
For more information, see section
on page
1 = 1 mm
0 … 200 mm
Setting range in mm
97.20
PWR ACK START
DLY
Power acknowledge start delay, that is, the time before the drive is ready to
start after the DI_IL circuit is closed. (DI_IL is the start interlock input of the
RMIO board.)
0 … 5 s
Setting range in seconds.
100 = 1 s
97.21
ZERO SPEED PTR
Zero speed pointer input for restarting the drive with the zero speed reference
used with the Brake match function created by DriveAP.
-255.255.31 …
+255.255.31 / C.-
32768 … C.32767
Parameter index or a constant value.
98 OPTION MODULES
Activation of the option modules.
The parameter settings will remain the same even though the application
macro is changed (parameter
).
98.01
ENCODER MODULE Activates the communication to the optional pulse encoder module. See also
NTAC
Communication active. Module type: NTAC module. Connection interface:
Fibre optic DDCS link.
Note:
Module node number must be set to 16. For directions, see the
NTAC-0x
Module
Installation and Start-up Guide
[3AFY58919730 (English)].
0
NO
Inactive
1
RTAC-SLOT1
Communication active. Module type: RTAC. Connection interface: Option
slot 1 of the drive.
2
RTAC-SLOT2
Communication active. Module type: RTAC. Connection interface: Option
slot 2 of the drive.
3
RTAC-DDCS
Communication active. Module type: RTAC. Connection interface: Optional I/O
module adapter (AIMA) that communicates with the drive through a fibre optic
DDCS link.
Note:
Module node number must be set to 16. For directions, see
RTAC-01
Pulse Encoder Interface User's Manual
[3AFE64486853 (English)].
4
RRIA-SLOT1
Communication active. Module type: RRIA. Connection interface: Option Slot 1
of the drive.
5
RRIA-SLOT2
Communication active. Module type: RRIA. Connection interface: Option Slot 2
of the drive.
6
Index
Name/Selection
Description
FbEq
Summary of Contents for ACS 800 Series
Page 1: ...ACS800 Firmware Manual Crane Control Program N697 ...
Page 4: ......
Page 26: ...Start up and control through the I O interface 26 ...
Page 36: ...Quick start up guide 36 ...
Page 52: ...Control panel 52 ...
Page 105: ...Program features 105 Figure Control diagram for Shaft synchronisation executed in 20 ms ...
Page 128: ...Program features 128 ...
Page 150: ...Application macros control location EXT1 EXT2 150 ...
Page 228: ...Actual signals and parameters 228 ...
Page 299: ...Adaptive Programming examples for crane control 299 ...
Page 305: ...Adaptive Programming examples for crane control 305 ...
Page 318: ...Analogue Extension Module 318 ...
Page 332: ...Additional data actual signals and parameters 332 ...
Page 334: ...DriveWindow 334 ...
Page 335: ...Control block diagrams 335 Control block diagrams ...
Page 336: ...Control block diagrams 336 ...
Page 337: ...Control block diagrams 337 ...
Page 338: ...Control block diagrams 338 ...
Page 340: ...www abb com drives www abb com drivespartners Contact us 3AFE68775230 Rev E EN 2012 09 25 ...