Program features
121
Start high logic
Warning
may be caused by the following conditions:
• Prevention of start during power-on sequence. The Crane control program
includes prevention of the crane start when the mains power is switched on. If the
crane start signal is TRUE during mains power switch-on, the drive indicates
warning
. Change the crane start signal to zero and give a
new crane start command.
• Use of fieldbus control bits in the wrong order. For more information, see section
Start/Stop sequence using communication bits
Diagnostics
Watchdog function
This function supervises the below-mentioned fault and alarm conditions and
generates a WATCH DOG BIT-N bit, which can be used for safety or emergency
interlocks. The drive is healthy when the bit is active (value = 1). When any of the
fault or alarm conditions get activated, the bit becomes inactive (value = 0). The fault
and alarm conditions used to generate the WATCH DOG BIT-N are listed below.
1. CPU HEALTHY
2. EXTERNAL FAULT (3.06 bit 8)
3. M_F COMM ERROR (3.3 bit 13)
4. BR OVER TEMP (3.17 bit 3)
5. BC OVER TEMP (3.17 bit 4)
6. BC SHORT CIRC (3.17 bit 2)
7. FB COMM ERROR (3.6 bit 12)
Diagnostics
Actual signal
Additional information
bit 14
START HIGH (FFB3): Crane start signal high when switching power ON or
starting against end limit logic sensor high
Actual signal
Additional information
bit 11
WATCH DOG-N active (bit = 0)
Summary of Contents for ACS 800 Series
Page 1: ...ACS800 Firmware Manual Crane Control Program N697 ...
Page 4: ......
Page 26: ...Start up and control through the I O interface 26 ...
Page 36: ...Quick start up guide 36 ...
Page 52: ...Control panel 52 ...
Page 105: ...Program features 105 Figure Control diagram for Shaft synchronisation executed in 20 ms ...
Page 128: ...Program features 128 ...
Page 150: ...Application macros control location EXT1 EXT2 150 ...
Page 228: ...Actual signals and parameters 228 ...
Page 299: ...Adaptive Programming examples for crane control 299 ...
Page 305: ...Adaptive Programming examples for crane control 305 ...
Page 318: ...Analogue Extension Module 318 ...
Page 332: ...Additional data actual signals and parameters 332 ...
Page 334: ...DriveWindow 334 ...
Page 335: ...Control block diagrams 335 Control block diagrams ...
Page 336: ...Control block diagrams 336 ...
Page 337: ...Control block diagrams 337 ...
Page 338: ...Control block diagrams 338 ...
Page 340: ...www abb com drives www abb com drivespartners Contact us 3AFE68775230 Rev E EN 2012 09 25 ...