Actual signals and parameters
213
TOFF
9
TON
8
TRIGG
6
XOR
4
84.06
INPUT1
Selects the source for input I1 of Block Parameter Set 1.
-255.255.31 …
+255.255.31 / C.-
32768 … C.32767
Parameter index or a constant value:
- Parameter pointer: Inversion, group, index and bit fields. The bit number is
effective only for blocks handling boolean inputs.
- Constant value: Inversion and constant fields. Inversion field must have value
C to enable the constant setting.
Example:
The state of digital input DI2 is connected to Input 1 as follows:
- Set the source selection parameter (84.06) to +.01.17.01. (The application
program stores the state of digital input DI2 to bit 1 of actual signal 01.17.)
- If you need an inverted value, switch the sign of the pointer value
(-01.17.01.).
-
84.07
INPUT2
See parameter
-255.255.31 …
+255.255.31 / C.-
32768 … C.32767
See parameter
-
84.08
INPUT3
See parameter
-255.255.31 …
+255.255.31 / C.-
32768 … C.32767
See parameter
-
84.09
OUTPUT
Stores and displays the output of Block Parameter Set 1.
…
…
84.79
OUTPUT
Stores the output of Block Parameter Set 15.
-
85 USER CONSTANTS
Storage of the Adaptive Program constants and messages. For more
information, see the
Adaptive Program Application Guide
[3AFE64527274
(English)].
85.01
CONSTANT1
Sets a constant for the Adaptive Program.
-8388608 to 8388607
Integer value
1 = 1
85.02
CONSTANT2
Sets a constant for the Adaptive Program.
-8388608 to 8388607
Integer value
1 = 1
85.03
CONSTANT3
Sets a constant for the Adaptive Program.
-8388608 to 8388607
Integer value
1 = 1
85.04
CONSTANT4
Sets a constant for the Adaptive Program.
-8388608 to 8388607
Integer value
1 = 1
85.05
CONSTANT5
Sets a constant for the Adaptive Program.
-8388608 to 8388607
Integer value
1 = 1
85.06
CONSTANT6
Sets a constant for the Adaptive Program.
-8388608 to 8388607
Integer value
1 = 1
85.07
CONSTANT7
Sets a constant for the Adaptive Program.
-8388608 to 8388607
Integer value
1 = 1
85.08
CONSTANT8
Sets a constant for the Adaptive Program.
-8388608 to 8388607
Integer value
1 = 1
Index
Name/Selection
Description
FbEq
Summary of Contents for ACS 800 Series
Page 1: ...ACS800 Firmware Manual Crane Control Program N697 ...
Page 4: ......
Page 26: ...Start up and control through the I O interface 26 ...
Page 36: ...Quick start up guide 36 ...
Page 52: ...Control panel 52 ...
Page 105: ...Program features 105 Figure Control diagram for Shaft synchronisation executed in 20 ms ...
Page 128: ...Program features 128 ...
Page 150: ...Application macros control location EXT1 EXT2 150 ...
Page 228: ...Actual signals and parameters 228 ...
Page 299: ...Adaptive Programming examples for crane control 299 ...
Page 305: ...Adaptive Programming examples for crane control 305 ...
Page 318: ...Analogue Extension Module 318 ...
Page 332: ...Additional data actual signals and parameters 332 ...
Page 334: ...DriveWindow 334 ...
Page 335: ...Control block diagrams 335 Control block diagrams ...
Page 336: ...Control block diagrams 336 ...
Page 337: ...Control block diagrams 337 ...
Page 338: ...Control block diagrams 338 ...
Page 340: ...www abb com drives www abb com drivespartners Contact us 3AFE68775230 Rev E EN 2012 09 25 ...