Appendix 1 Parameter table
APPENDIX 388
Group
Parameter
Number
Name
Setting Range
Default
Page
11-07
P.327
PM motor type
0: SPM
0
1: IPM
11-08
P.328
PM motor initial position detection
method
0: Pull in.
0
1: High frequency pulse
11-09
P.329
PM motor acceleration id
0~200%
80%
11-10
P.330
PM motor constant speed id
0~200%
0%
11-11
P.331
PM motor estimated speed filtering
time
0~1000ms
2ms
11-12
P.401
Torque command
-400.0~400.0%
0.0%
11-13
P.402
Speed limit
-120%~120%
0%
11-14
P.403
Speed limit bias
0~120%
10%
11-15
P.404
Torque filter time
0~1000ms
0ms
11-16
P.405
Torque command source
0: Given by 11-12(P.401).
0
1: Given by analog or pulse input.
2: Given by communication mode.
11-17
P.406
Speed limit selection
0: Speed is limited according to 11-13 (P.402)
and 11-14 (P.403)
0
1: Frequency command source(it is decided
according to 00-16(P.79) )
11-18
P.407
Unidirectional speed limit bias
0: Off
1
1: Unidirectional speed limit bias is valid.
11-19
P.408
Forward-rotation electronic torque
limit
0~400.0%
200.0%
11-20
P.409
Reverse-rotation regenerative
torque limit
0~400.0%
200.0%
11-21
P.410
Reverse-rotation electronic torque
limit
0~400.0%
200.0%
11-22
P.411
Forward-rotation regenerative
torque limit
0~400.0%
200.0%
11-23
P.412
Zero-speed proportional coefficient
0~2000.0
100.0
272
11-24
P.413
Zero-speed integral time
0~20.00s
0.30s
272
11-25
P.414
Zero-speed switching frequency
0~650.00Hz
5.00Hz
272
11-26
P.415
IM motor estimated speed filtering
time
0-100.00ms
0
11-30
P.371
Second motor speed control
proportional coefficient 1
0~2000
100
99999
11-31
P.372
Second motor speed control integral
time 1
0~20.00s
0.30s
99999
11-32
P.373
Second motor PI coefficient
switch-over frequency 1
0~11-35 (P.376)Hz
5.00Hz
99999
11-33
P.374
Second motor speed control
proportional coefficient 2
0~2000
100
99999
11-34
P.375
Second motor speed control integral
time 2
0~20.00s
0.30s
99999
11-35
P.376
Second motor PI coefficient
switch-over frequency 2
11-32(P.373)~650.00Hz
10.00Hz
99999