System parameter group 00
PARAMETER DESCRIPTION 85
6: User registered parameter 15-00(P.900)~15-19(P.919) and the parameters set in 15-00(P.900)~15-19(P.919)
and the parameters in table 1 above will not be restored to default values. After parameters are restored,
00-02(P.996~P.999) is reset to 0.
Note: When the parameter is restored to default value or some of the parameters are restored to default value, be sure
to wait for the screen to display
, which means that it’s complete, and then perform other operations.
5.1.3 Parameter protection
It is used to select whether parameters can be written to prevent changing parameter values due to disoperation.
Parameter
Name
Default Setting Range
Content
00-03
P.77
Selection of
parameters write
protection
0
0
Parameters can be written only when the motor stops.
1
Parameters cannot be written.
2
Parameters can also be written when the motor is running.
3
Parameters cannot be read when in password protection.
00-04
P.294
Password parameter
0
0~65535
Write the registered password to decrypt parameter
protection.
00-05
P.295
Password setup
0
0~65535
Register password for parameter protection setting.
Selection of parameters write protectio
n
Write parameters only during stop (00-03(P.77)=“0”initial value)
Exception
When running, the parameters below can still be written:
Group
No.
Name
Group
No.
Name
00-03
P.77
Selection of parameters write protection
02-25
P.198
Terminal 4-5 minimum input current/ voltage
00-07
P.161
Multi-function display
02-26
P.199
Terminal 4-5 maximum input current/ voltage
02-04
P.54
Terminal AM1 output function
02-27
P.196
Percentage corresponds to terminal 4-5
minimum input current/ voltage
02-05
P.537
Terminal AM2 output function
02-12
P.192
Terminal 2-5 minimum input positive voltage
02-28
P.197
Percentage corresponds to terminal 4-5
maximum input current/ voltage
02-13
P.193
Terminal 2-5 maximum input positive voltage
02-14
P.194
Percentage corresponds to terminal 2-5 minimum
positive voltage
02-34
P.548
Terminal 3-5 minimum input current/ voltage
02-35
P.549
Terminal 3-5 maximum input current/ voltage
02-15
P.195
Percentage corresponds to terminal 2-5
maximum positive voltage
02-36
P.546
Percentage corresponds to terminal 3-5
minimum input current/ voltage
02-16
P.512
Terminal 2-5 minimum input negative voltage
02-37
P.547
Percentage corresponds to terminal 3-5
maximum input current/ voltage
02-17
P.513
Terminal 2-5 maximum input negative voltage
02-18
P.510
Percentage corresponds to terminal 2-5 minimum
negative voltage
02-39
P.524
Terminal HDI minimum input frequency
02-40
P.525
Terminal HDI maximum input frequency
02-19
P.511
Percentage corresponds to terminal 2-5
maximum negative voltage
02-41
P.522
Percentage corresponds to terminal HDI
minimum input frequency
02-42
P.523
Percentage corresponds to terminal HDI
maximum input frequency
04-20
P.132
Programmed operation mode speed 2
04-21
P.133
Programmed operation mode speed3
02-44
P.543
Terminal FM output function selection
04-22
P.134
Programmed operation mode speed 4
Setting