Appendix 1 Parameter table
APPENDIX 385
Group
Parameter
Number
Name
Setting Range
Default Page
10-18
P.229
Dwell function selection
0: Off.
0
1: Backlash compensation function.
2: Acceleration and deceleration interrupt waiting
function.
10-19
P.230
Dwell frequency at acceleration
0~650.00Hz
1.00Hz
10-20
P.231
Dwell time at acceleration
0~360.0s
0.5s
10-21
P.232
Dwell frequency at deceleration
0~650.00Hz
1.00Hz
10-22
P.233
Dwell time at deceleration
0~360.0s
0.5s
10-23
P.234
Triangular wave function selection
0: Off.
0
1: If terminal function TRI is triggered, triangular
wave function will on.
2: Triangular wave function is on at all time.
10-24
P.235
Maximum amplitude
0~25.0%
10.0%
10-25
P.236
Amplitude compensation at
deceleration
0~50.0%
10.0%
10-26
P.237
Amplitude compensation at
acceleration
0~50.0%
10.0%
10-27
P.238
Amplitude acceleration time
0~360.00s/0~3600.0s
10.00s
10-28
P.239
Amplitude deceleration time
0~360.00s/0~3600.0s
10.00s
10-29
P.247
Switch to commercial supply MC
switch-over interlock time
0.1~100.0s
1.0s
10-30
P.248
Switch to commercial supply
waiting time
0.1~100.0s
0.5s
10-31
P.249
From inverter to commercial power
supply switch-over frequency
0~60.00Hz
99999
99999: Off.
10-32
P.250
Automatic switch-over frequency
range
0~10.00Hz: After switching from inverter
operation to commercial power supply operation,
after inverter start command (STF/STR) is OFF,
switch to inverter operation.
99999
99999: After switching from inverter operation to
commercial power supply operation, after
inverter start command (STF/STR) is OFF,
switch to inverter operation, and slow down to
stop.
10-33
P.273
When input power fail stop option
0: Off.
0
1: No under-voltage avoidance (If under-voltage
or power fail, the motor decelerates to stop.)
2: No under-voltage avoidance (If under-voltage
or power fail, the motor decelerates to stop.
Motor re-accelerates if power restores during
the deceleration to stop.)
11: under-voltage avoidance If under-voltage or
power fail, the motor decelerates to stop.)
12: under-voltage avoidance (If under-voltage or
power fail, the motor decelerates to stop.
Motor re-accelerates if power restores during
the deceleration to stop.)