Appendix 1 Parameter table
APPENDIX 322
Parameter
Number
Group
Name
Setting Range
Default
Page
P.66
06-03
Stall prevention operation
reduction starting
frequency
50Hz system: 0~650.00Hz
50.00Hz
60Hz system: 0~650.00Hz
60.00Hz
P.67
10-13
Auto reset times
0: Off.
0
1~10: If the alarm exceeds 10-13(P.67) times,
inverter will not reset.
P.68
10-14
Auto reset waiting time
0~360.0s
1.0s
P.69
10-15
Auto reset times count
Read only
0
P.70
06-06
Special regenerative
brake duty
0~100.0%
0.0%
P.71
00-13
Idling brake / DC brake
0: Idling brake
1
1: DC brake
P.72
00-11
Carrier frequency
Frame A/B: 1~15 kHz
5 kHz
Frame C: 1~9 kHz
5 kHz
Frame D/E: 1~9 kHz
4 kHz
Frame F/G: 1~9 kHz
2 kHz
Frame H: 1~6 kHz
2 kHz
P.73
02-08
Terminal 2-5 signal range
selection
0: Signal sampling range from 0 ~5V.
1
1: Signal sampling range
from 0 ~10V.
2: Signal sampling range from 0 ~ -5V.
3: Signal sampling range from 0 ~ -10V.
4: Signal sampling range from -5~+5V.
5: Signal sampling range from -10~+10V.
P.74
02-43
Terminal HDO clock
multiplier factor
0: Select FM function as the output function of
terminal HDO.
0
1~9000: factor for square-wave pulse output
frequency. Value in 02-43 (P.74) times output
frequency will be actual output pulse frequency.
P.75
00-14
Stop function selection
0: Press STOP button and inverter stop running in
PU and H2 mode
1
1: Press STOP button and inverter stop running in
all mode.
P.77
00-03
Selection of parameters
write protection
0: Parameters can be written only when the motor
stops.
0
1: Parameters cannot be written.
2: Parameters can also be written when the motor
is running.
3: Parameters cannot be read when in password
protection.
P.78
00-15
Prevent forward/reverse
rotation selection
0: Forward/reverse rotation are both permitted.
0
1: Prevent reverse rotation (Giving reverse signal
decelerates and stops the motor).
2: Prevent forward rotation (Giving forward signal
decelerates and stops the motor).