PID parameter group 08
PARAMETER DESCRIPTION 224
Group
Parameter
Number
Name
Setting Range
Default Page
08-27
P.714
PID deviation control limit
0~100.00%
0.00%
08-28
P.715
Integral separated property
0: Off
0
1: Integral separated
08-29
P.716
Integral separated point
0~100.00%
50.00%
08-30
P.717
PID differential limit
0~100.00%
0.10%
08-31
P.718
PID output positive deviation limit
0~100.00%
100.0%
08-32
P.719
PID output negative deviation limit
0~100.00%
100.0%
08-33
P.720
PID parameter switch-over operation
selection
0: No PID parameter switch-over.
0
1: PID parameter switch-over based on
deviation.
08-34
P.721
PID parameter switch-over deviation
lower limit
0~100.00%
20.00%
08-35
P.722
PID parameter switch-over deviation
upper limit
0~100.00%
80.00%
08-36
P.723
PID disconnection operation option 1
0: Select no need to run to the upper limit
when PID is disconnected
1
1: Select need to run to the upper limit when
PID is disconnected
08-39
P.726
PID counting when inverter stop action
selection
0: PID stop counting when inverter stop
0
1: PID keep counting when inverter stop
08-40
P.727
PID allowed reverse rotation action
selection
0: PID does not allow reverse rotation
0
1: PID allows reverse rotation
08-41
P.728
PID in reverse direction integral limit
0~100.0%
0.0%
08-42
P.729
PID minimum output frequency
0~10.00Hz
0.00Hz
08-43
P.251
PID pressure range (Bar) setting
1.0~100.0
100.0
08-44
P.252
PID unit selAection
0: %
0
1: bar
2: --
3: kgs
4: kg
5: psi
6: Pa
7: kPa
8: MPa
9: C
08-45
P.253
Disconnection detection time feedback
0.0~600.0s
0.0s
08-46
P.254
Disconnection processing method
feedback
0: AEr alarm, inverter free stop
0
1: Slow down and stop, call AEr alarm
2: AEr alerts and continues running
08-50
P.724
PID target linear change time
0~650.00s
0.00s