Analog input and output parameter group 02
PARAMETER DESCRIPTION 115
5.3 Analog input and output parameter group 02
Group
Parameter
Number
Name
Setting Range
Default
Page
02-00
P.500
Terminal 2-5 input function
0: Off
1
1: Frequency command
2: Torque command
3: PID target value
4: PID feedback signal
5: Tension target value
6: Line speed
7: Line speed feedback
8: Real-time roll diameter
9: Initial roll diameter
10: Material thickness
11: PTC thermistor
12: PT100 thermistor
13: VF separate function
14: Positive torque limit
15: Negative torque limit
16: Positive/Negative torque limit
17: Regenerative torque limit
02-01
P.501
Terminal 4-5
input
function
Same as 02-00(P.500)
1
02-02
P.504
Terminal 3-5 input function Same as 02-00(P.500)
0
02-03
P.503
Terminal HDI input function Same as 02-00(P.500)
0
02-04
P.54
Terminal AM1 output
function
0: Output frequency, use 02-51 (P.55) value as 100%.
0
1: Output current, use 02-52 (P.56) value as 100%.
2: Output DC bus voltage, use the
OV trigger voltage
as 100%.
3: Output inverter temperature accumulate rising rate,
use NTC trigger level as 100%.
4: Output inverter thermal relay accumulate rate, use
the digital thermal relay trigger level ( 06-00 ( P.9 ) ≠
0 ) or the thermal relay on IGBT trigger level ( 06-00
(P.9) = 0) as 100%.
5: Target frequency, use 02-51(P.55) value as 100%.
6: Fixed output, voltage or current output level can be
set by 02-54 (P.541)
7: Output voltage, use inverter rated voltage as 100%
8: Excitation current, use motor rated current as 100%.
(Valid only when 00-21(P.300) or 00-22 (P.370) is set to
3~6)