Appendix 1 Parameter table
APPENDIX 333
Parameter
Number
Group
Name
Setting Range
Default
Page
P.239
10-28
Amplitude deceleration
time
0~360.00s/0~3600.0s
10.00s
P.240
02-07
Auxiliary frequency
0: Off
0
1: Output frequency = basic fre auxiliary
frequency (given by terminal 2-5)
2: Output frequency = basic fre auxiliary
frequency (given by terminal 4-5)
3: Output frequency = basic frequency - auxiliary
frequency (given by terminal 2-5)
4: Output frequency = basic frequency - auxiliary
frequency (given by 4-5 terminal)
5: Output frequency = proportional linkage signal
(
given by terminal 2-5)
6: Output frequency = proportional linkage signal
(given by terminal 4-5)
7: Output frequency = proportional linkage signal
(
given by terminal 3-5)
8: Output frequency = basic fre auxiliary
frequency (given by terminal 3-5)
9: Output frequency = basic frequency - auxiliary
frequency (given by terminal 3-5)
P.241
08-02
PID sampling period
0~60000 ms
20 ms
P.242
10-05
DC brake before inverter
start
0: Off
0
1: Before starting operate DC brake first.
P.243
10-06
DC brake time before
inverter start
0~60.0s
0.5s
P.244
10-07
DC brake voltage before
inverter start
0~30.0%: 7.5K/11KF and below
4.0%
0~30.0%: 11K/15KF~55K/75KF
2.0%
0~30.0%: 75K/90KF and above.
1.0%
P.245
06-12
Cooling fan operation
0X: Inverter shows FAN alarm when fan is
damaged.
0
1X: Inverter don’t alarm when fan is damaged, but
the output terminal which is set to function 16 will
output a signal.
X0: Fan turn on when inverter starts running. Fan
turn off 30 seconds after inverter stops.
X1: Fan turn on when inverter power on. Fan turn
off when inverter power off.
X2: Fan turn on if heat sink temperature is higher
than 40℃. Fan turn off when inverter power off.
X3: Fan turn on if heat sink temperature is higher
than 60℃. Fan turn off when heat sink
temperature is lower than 40℃.
P.246
13-01
Modulation coefficient
0.90~1.20
1.00