Analog input and output parameter group 02
PARAMETER DESCRIPTION 118
Group
Parameter
Number
Name
Setting Range
Default Page
02-31
P.527
Terminal 3-5 filter time
0~2000ms
30ms
02-32
P.507
Terminal 3-5
current/voltage signal
bias
rate
-100.0%~100.0%
0.0%
02-33
P.545
Terminal 3-5 disconnect
selection
0: Off.
0
1: Inverter decelerates to 0Hz, muti-function digital
output terminal set off alarm
2: Inverter stops immediately, and keypad displays
“AEr” alarm
3: Inverter runs continuously according to the frequency
reference before disconnection. Digital output terminal
will set off alarm.
02-34
P.548
Terminal 3-5 minimum
input current/ voltage
0~10.00V
0.00V
02-35
P.549
Terminal 3-5 maximum
input current/ voltage
0~10.00V
10.00V
02-36
P.546
Percentage corresponds to
terminal 3-5 minimum input
current/ voltage
-100.0%~100.0%
0.0%
-400.0%~400.0%(02-00(P.500)= 2/14/15/16/17)
02-37
P.547
Percentage corresponds to
terminal 3-5 maximum
input current/ voltage
-100.0%~100.0%
100.0%
-400.0%~400.0%(02-00(P.500)= 2/14/15/16/17)
02-38
P.526
Terminal HDI filter time
0~2000ms
10ms
02-39
P.524
Terminal HDI minimum
input frequency
0~100.00kHz
0.00kHz
02-40
P.525
Terminal HDI maximum
input frequency
0~100.00kHz
100.00
kHz
02-41
P.522
Percentage corresponds to
terminal HDI minimum
input frequency
-100.0%~100.0%
0.0%
-400.0%~400.0%(02-00(P.500)= 2/14/15/16/17)
02-42
P.523
Percentage corresponds to
terminal HDI maximum
input frequency
-100.0%~100.0%
100.0%
-400.0%~400.0%(02-00(P.500)= 2/14/15/16/17)
02-43
P.74
Terminal HDO clock
multiplier factor
0: Select FM function as the output function of terminal
HDO.
0
1~9000: factor for square-wave pulse output
frequency. Value in 02-43 (P.74) times output frequency
will be actual output pulse frequency.
02-44
P.543
Terminal
FM
output
function selection
0: Output frequency, use 02-51 (P.55) value as 100%.
0
1: Output current, use 02-52 (P.56) value as 100%.
2: Output DC bus voltage, use the
OV trigger voltage as
100%.