Protection parameter group 06
PARAMETER DESCRIPTION 193
5.7.13 Output phase loss protection
Turn on output phase loss protection function.
Parameter
Name
Default Setting Range
Content
06-20
P.262
Output phase loss
protection
0
0
Off
1
When output phase loss, inverter stops and alarms LF.
Output phase loss protection
06-20(P.262)=“1”, When output phase loss, inverter stops and alarms”LF”; when 06-20(P.262)=“0”, the function
will be off.
5.7.14 Low voltage protection
Control the low voltage level by parameter.
Parameter
Name
Default Setting Range
Content
06-21
P.705
Low voltage level
155V
155~220V
220V
310V
310~440V
440V
Low voltage level
When inverter input voltage is too low, which the DC bus voltage lower than 06-21(P.705)
value, inverter enters
low voltage protection state, it will stop output and idle stop.
5.7.15 Regenerative brake operation level
Set regenerative brake operation level by parameter.
Parameter
Name
Default Setting Range
Content
06-22
P.706
Regenerative brake
operation level
360V
205~400V
220V
720V
410~800V
440V
Regenerative brake operation level
06-22(P.706) is regenerative brake (brake resistor) operation level. When DC bus voltage is over 06-22(P.706)
value, regenerative brake (brake resistor) operation starts.
5.7.16 Voltage stall level
Set voltage stall operation level.
Parameter
Name
Default Setting Range
Content
06-23
P.707
Voltage stall level
380V
205~400V
220V type
760V
410~800V
440V type
Voltage stall level
When inverter output voltage is over 06-23(P.707)
set value, it is in voltage stall state.
Setting
Setting
Setting