Application parameter group 10
PARAMETER DESCRIPTION 246
Group
Parameter
Number
Name
Setting Range
Default
Page
10-24
P.235
Maximum amplitude
0~25.0%
10.0%
10-25
P.236
Amplitude compensation at
deceleration
0~50.0%
10.0%
10-26
P.237
Amplitude compensation at
acceleration
0~50.0%
10.0%
10-27
P.238
Amplitude acceleration time
0~360.00s/0~3600.0s
10.00s
10-28
P.239
Amplitude deceleration time
0~360.00s/0~3600.0s
10.00s
10-29
P.247
Switch to commercial supply
MC switch-over interlock
time
0.1~100.0s
1.0s
10-30
P.248
Switch to commercial supply
waiting time
0.1~100.0s
0.5s
10-31
P.249
From inverter to commercial
power supply switch-over
frequency
0~60.00Hz
99999
99999: Off.
10-32
P.250
Automatic switch-over
frequency range
0~10.00Hz: After switching from inverter
operation to commercial power supply operation,
after inverter start command (STF/STR) is OFF,
switch to inverter operation.
99999
99999: After switching from inverter operation to
commercial power supply operation, after
inverter start command (STF/STR) is OFF,
switch to inverter operation, and slow down to
stop.
10-33
P.273
When input power fail stop
option
0: Off.
0
1: No under-voltage avoidance (If under-voltage
or power fail, the motor decelerates to stop.)
2: No under-voltage avoidance (If under-voltage
or power fail, the motor decelerates to stop.
Motor re-accelerates if power restores during
the deceleration to stop.)
11: under-voltage avoidance If under-voltage or
power fail, the motor decelerates to stop.)
12: under-voltage avoidance (If under-voltage or
power fail, the motor decelerates to stop.
Motor re-accelerates if power restores during
the deceleration to stop.)