Communication parameter group 07
PARAMETER DESCRIPTION 212
Normal response
Mode
Start
Address*1) Function*2)
Readout data
number *5)
Readout data*6)
Check
Stop
ASCII
H3A
2char
2char
2char
4char
…2N×8bit
2char
0D 0A
RTU
>=10ms
8bit
8bit
1byte
2byte
…N×8bit
2byte
>=10ms
Message
Content
*1)Address
Set the address for sending information, 0 is invalid
*2)Function code
H03
*3)Start address
Set the address of the register to be read
*4)Number of registers
Set the number of registers to be read. The maximum number is 20.
*5)Read data number
Twice as much as *4)
*6)Read data
Set the data specified in *4)and read the data from high byte to low byte.
2.
Data write in (H06)
Mode
Start
Address*1) Function*2) Start Address*3)
Write-in data*4)
Check
Stop
ASCII
H3A
2char
2char
4char
4char
2char
0D 0A
RTU
>=10ms
8bit
8bit
2byte
2byte
2byte
>=10ms
Normal response
Mode
Start
Address*1) Function*2) Start Address*3)
Write-in data*4)
Check
Stop
ASCII
H3A
2char
2char
4char
4char
2char
0D 0A
RTU
>=10ms
8bit
8bit
2byte
2byte
2byte
>=10ms
Message
Content
*1)Address
Set the address for sending information
*2)Function code
H06
*3)Start address
Set as the start address of the register that needs to be written
*4)Write data
Write data to the specified register, fixed at 16bit.
Note: The content of normal response is the same as query information.
3.
Write multiple registers (H10)
Mode Start
Address
*1)
Function
*2)
Start
Address *3)
Number of
register *4)
Data*5)
Write-in data *6)
Check Stop
ASCII H3A
2char
2char
4char
4char
2char
4char …2N×8bit
2char
0D 0A
RTU
>=10ms 8bit
8bit
2byte
2byte
1byte
2byte …N×16bit
2byte
>=10ms
Normal response
Mode
Start
Address*1) Function*2) Start Address*3) Number of register *4) Check
Stop
ASCII
H3A
2char
2char
4char
4char
2char
0D 0A
RTU
>=10ms
8bit
8bit
2byte
2byte
2byte
>=10ms
Message
Content
*1)Address
Set the address for sending information
*2)Function code
H10
*3)Start address
Set as the start address for the register that needs to be written