Motor parameter group 05
PARAMETER DESCRIPTION 178
Note: 1. Before executing the IM motor inertia automatic measurement function, please follow 5.6.1 to perform the IM
motor parameters automatic measurement function and set 00-21(P.300)=4 first.
2. Before executing the PM motor inertia automatic measurement function, please perform the PM motor parameter
automatic measurement function and Z-phase position automatic measurement function according to 5.6.1 and set
00-21(P.300)=5.
3. Before executing the automatic inertia measurement function, please set a reasonable value of 05-17(P.318)
according to the inertia of the motor.
4. If the inertia measurement is abnormal, please adjust the value of 05-19(P.391)~05-21(P.393) appropriately.
5.6.4 Second motor parameter
By setting second motor parameter and matching digital input terminal, automatic measurement function of second
motor parameters can be performed.
Parameter
Name
Default Setting Range
Content
05-22
P.332
Second motor rated
power
99999
0~650.00kW
---
99999
Off.
05-23
P.333
Second motor poles
99999
0~48
---
99999
Off.
05-24
P.334
Second motor rated
voltage
99999
0~510V
440V
0~255V
220V
99999
Off.
05-25
P.335
Second motor rated
frequency
99999
0~650.00Hz
---
99999
Off.
05-26
P.336
Second motor rated
current
99999
0~500.00A
Below Frame G
0~5000.0A
Frame G and above
99999
Off.
05-27
P.337
Second motor rated
rotation speed
99999
0~65000r/min
---
99999
Off.
05-28
P.338
Second motor
excitation current
99999
0~500.00A
Below Frame G
0~5000.0A
Frame G and above
99999
Off.