Basic operation steps for different modes
BASIC OPERATION 72
4.3 Basic operation steps for different modes
4.3.1 Basic operation steps for PU mode (00-16(P.79)=0 or 1)
Step
Description
1
• Switch operation mode to PU mode, and indicator in
PU
will light up.
Note: 1. When 00-16(P.79) =0, the inverter will first be in external mode after power on or reset.
2. For selecting and switching operation mode, please refer to section
4.2
.
2
• Enter frequency setting mode and write target frequency into memory.
Note: For detailed setting procedures, please refer to section 4.2.4.
3
• Press
FWD
or
REV
to run the motor. At this point, indicator in
FWD
or
REV
will flash to indicate that
the motor is running. The keypad will automatically switch to monitor mode and display the current output
frequency.
Note: 1. For detailed operation steps for monitoring mode, please refer to section 4.2.3.
2. While the motor is running, the user can enter frequency setting mode to change target frequency for
regulating the motor speed.
4
•
Press
RESET
STOP
and the motor will begin to decelerate until it comes to a full stop.
• Indicator in
FWD
or
REV
will not turn off until the inverter stops outputting voltage.
4.3.2 Basic operation steps for external mode (00-16(P.79)=0 or 2)
Step
Description
1
• Switch operation mode to external mode, screen will display
and indicator in
EXT
will light up.
Note: 1.When 00-16(P.79) =0, after power on or reset, press
MODE
to switch to operation mode, inverter will
first switch to external mode, then use dial or up down key to switch to PU mode;
2. When 00-16(P.79) =2, inverter will always be in external mode ;
3. For selecting and switching operation mode, please refer to section 4.2
.
2
•
The target frequency is set by external terminal (the default priority is from high to low)
• If the program operation mode is selected, refer to section 5.4.1 Digital Input Function Option and section
5.5.2 Program Operation Mode.
• If target frequency is set by multi-speed , refer to section 5.5.1 Multi-speed 16.
• If target frequency is set by A2/B2 terminal input signal setting of PG card, refer to section 5.10.4 PG2
Parameter.
• If target frequency is set by PWM pulse input, refer to section 5.4.1 Digital Input Function Selection.
•If target frequency is set by 2-5 terminal input signal, refer to section 5.3.5 2-5 Input Selection and Processing.
•If target frequency is set by 4-5 terminal input signal, refer to section 5.3.6 4-5 Input Selection and Processing.
•If target frequency is set by 3-5 terminal input signal, refer to section 5.3.7 4-5 Input Selection and Processing.
•If target frequency is set by HDI terminal high-speed pulse input, refer to section 5.3.8 HDI Input Selection and
Processing.
3
•
Turn on STF or STR to run the motor.
• At this point, indicator in
FWD
or
REV
will flash, indicating that the motor is running.
Note: 1. For setting up the starting terminals STF and STR, please refer to 00-15(P.78) in chapter 5.1.8
Forward/reverse rotate prevent function and 5.4.1 function selection of digital input.
2. For detailed operation steps for the monitor mode, please refer to section 4.2.3.
3. If programmed operation mode is chosen, then STF and STR will become the starting signal and the
pause signal, instead of being forward or reverse terminals
.
4
•
Turn off STF or STR to decelerate the motor until it comes to a full stop.
• Indicator in
FWD
or
REV
will not turn off until the inverter stops outputting voltage.