Communication parameter group 07
PARAMETER DESCRIPTION 217
Item
Shihlin protocol
command code
Modbus
command code
Modbus
address
Data content and function description
Parameter clear
HFC
H06/
H10
H1104
H5A5A
Please refer to parameter
recovery table for details.
H5566
H5959
H1103
H9966
H1106
H9696
H99AA
H9A9A
H1105
H55AA
H1102
HA5A5
Parameter
read-out
H00~H63
H03
P mode:
H0000~H0513
Parameter
group mode:
H2710~H2D4F
1.Please refer to the parameter table for data
range and decimal point position
2. Modbus address of each parameter in P
parameter mode corresponds to hexadecimal
value of parameter number.
For example,
Modbus address of 04-26 (P.138) is H008A.
3.Modbus address of each parameter in
parameter group mode corresponds to
hexadecimal value of parameter 10000.
For example, Modbus address of 04-26 (P.138) is
0x28BA.
Parameter
write-in
H80~HE3
H06/
H10
Line speed
feedback read-out
---
H03
H100A
H0000~HFDE8
Line speed
feedback write-in
H06/H10
Line speed target
value read-out
---
H03
H100B
H0000~HFDE8
Line speed target
value write-in
H06/H10
Tension signal
read-out
---
H03
H100C
H0000~H7530
Tension signal
write-in
H06/H10
Torque command
read-out
---
H03
H100D
H0000~H0FA0 (0~400.0%)
HF060~HFFFF(-400.0%~0)
Torque command
write-in
H06/H10
Asynchronous
serial
communication
test
---
H08
H0000 (sub
function code for
loop-back test)
This content can be any numerical value
(H0000~HFFFF)
Operation
command write-in
HFA
H06/
H10
H1001
H0000~HFFFF
b8~b15: reserved
b7: inverter emergency stop (MRS)
b6: second function (RT)
b5: high speed (RH)
b4: medium speed (RM)
b3: low speed (RL)
b2: reverse rotation (STR)
b1: forward rotation (STF)
b0: reserved