Communication parameter group 07
PARAMETER DESCRIPTION 215
Step 2: After receive and processing the data without error, inverter will send a reply to upper controller:
Mode
Start
Address
Function Start address
Write data
Check
Stop
ASCII
H3A
H30 H31
H30 H36
H30H30
H43 H33
H31 H33
H38 H38
H39 H42
0D 0A
RTU
>=10ms
01
06
00
C3
13
88
74 A0
>=10ms
Example 4. Upper controller read parameters 01-10(P.0), 01-00(P.1), 01-01(P.2), 01-03(P.3), 04-00~04-02(P.4~P.6),
01-06~01-07(P.7~P.8), 06-00(P.9),10-00~10-01(P.10~P.11).
Step 1: Upper controller sends message to inverter for reading 01-10(P.0), 01-00(P.1), 01-01(P.2), 01-03(P.3),
04-00~04-02(P.4~P.6), 01-06~01-07(P.7~P.8), 06-00(P.9), 10-00~10-01(P.10~P.11) value. Start address
is H0000.
Mode
Start
Address
Function Start address
Number of registers
Check
Stop
ASCII
H3A
H30 H31
H30 H33
H30H30
H30 H30
H30 H30
H30 H43
H46 H30
0D 0A
RTU
>=10ms
01
03
00
00
00
0C
45 CF
>=10ms
Step 2: After receive and processing the data without error, inverter will send a reply to upper controller:
Mode
Start
Address
Function Number of data read
Read out data
Check
Stop
ASCII
H3A
H30 H31
H30 H33
H31 H38
…12×4 char
2char
0D 0A
RTU
>=10ms
01
03
18
…12×2 byte
2byte
>=10ms
Example 5. Upper controller write parameters 01-10(P.0), 01-00(P.1), 01-01(P.2), 01-03(P.3), 04-00~04-02(P.4~P.6),
01-06~01-07(P.7~P.8), 06-00(P.9), 10-00~10-01(P.10~P.11).
Step 1: Upper controller sends message to inverter for writing 01-10(P.0), 01-00(P.1), 01-01(P.2), 01-03(P.3),
04-00~04-02(P.4~P.6), 01-06~01-07/P.7~P.8, 06-00(P.9),10-00~10-01(P.10~P.11).
Mode Starting Address Function Start address
Number of
registers
Data
volume
Write-in data Check Stop
ASCII
H3A
H30 H31 H31 H30
H30
H30
H30
H30
H30
H30
H30
H43
H31 H38 …N×4 char
2char
0D 0A
RTU
>=10ms
01
10
00
00
00
0C
18
…N×2 byte
2byte
>=10ms
Step 2: After receive and processing the data without error, inverter will send a reply to upper controller:
Mode
Start
Address
Function Start address
Number of registers
Check
Stop
ASCII
H3A
H30 H31
H31 H30
H30H30
H30 H30
H30 H30
H30 H43
H45 H33
0D 0A
RTU
>=10ms
01
10
00
00
00
0C
00 18
>=10ms
Note: In above examples, parameters 02-15(P.195)reading and writing are all using P parameter mode. To use
parameter group mode, please note the difference in address. Please refer to the communication command list for
relevant contents.