Application parameter group 10
PARAMETER DESCRIPTION 245
Group
Parameter
Number
Name
Setting Range
Default
Page
10-11
P.61
Remote control function
0: Off
0
X1: Remote control function, frequency save in memory
X2: Remote control function, frequency won’t save
X3: Remote control function, frequency won’t save,
clear frequency setting every time STF/STR “turn
off”.
X4:Remote control function, frequency will be
memorized every 5s.
1X: Target frequency 01-01(P.2)~01-00(P.1),target
frequency value for RH, RM setting
10-12
P.65
Auto reset function
0: Off.
0
1: When over-voltage, inverter will reset.
2: When over-current, inverter will reset.
3: When either over-voltage or over-current, inverter will
reset.
4: When any alarm occur, inverter will reset.
10-13
P.67
Auto reset times
0: Off.
0
1~10: If the alarm exceeds 10-13(P.67) times, inverter
will not reset.
10-14
P.68
Auto reset waiting time
0~360.0s
1.0s
10-15
P.69
Auto reset times count
Read only
0
10-16
P.119
Forward and reverse
rotation
dead time
0~3000.0s
0.0s
10-17
P.159
Energy-saving control
function
0: Off.
0
1: Energy-saving mode.
10-18
P.229
Dwell function selection
0: Off.
0
1: Backlash compensation function.
2: Acceleration and deceleration interrupt waiting
function.
10-19
P.230
Dwell frequency at
acceleration
0~650.00Hz
1.00Hz
10-20
P.231
Dwell time at acceleration 0~360.0s
0.5s
10-21
P.232
Dwell frequency at
deceleration
0~650.00Hz
1.00Hz
10-22
P.233
Dwell time at
deceleration
0~360.0s
0.5s
10-23
P.234
Triangular wave function
selection
0: Off.
0
1: If terminal function TRI is triggered, triangular wave
function will on.
2: Triangular wave function is on at all time.