System parameter group 00
PARAMETER DESCRIPTION 79
Group
Parameter
Number
Parameter
Name
Setting Range
Default Page
00-07
P.161
Multi-function display
5: Running frequency (Hz)
0
6: Electronic thermal accumulation rate (%)
7: Signal value (V) of 2-5 input terminals.
8: Signal value (mA) of 4-5 input terminals (mA/V).
9: Output power (kW).
10: PG card feedback rotation speed. (Hz)
11: Forward reverse rotation signal. 1: forward
rotation 2: reverse rotation 0: stop.
12: NTC temperature (℃)
13: Motor electronic thermal accumulation rate (%)
14: Reserved.
15: Input frequency of terminal HDI. (kHz)
16: Real-time roll diameter. (mm)
17: Real-time line speed. (m/min)
18: Output torque of inverter (%)(Valid only when
00-21 (P. 300) or 00-22 (P. 370) is set to 3 ~ 6 )
19: Digital terminal input state
20: Digital terminal output state
21: Actual working carrier frequency
22: Signal value (mA) of 3-5 input terminals. (mA/V)
23: Synchronous motor rotor pole position(Show
motor rotor magnetic pole position from encoder
feedback, valid when 00-21 (P. 300) = 5)
24: Current target frequency
25: PTC input percentage
26: Target pressure and feedback pressure from the
constant pressure system
27: Motor rotation speed
28: Power factor
29: Power accumulation rate (kWh)
30: PG feedback rotation speed
31: Motor rotor position (Z pulse as 0)
32: PG card feedback A1 B1 pulse count
33:
PG card feedback A2 B2 pulse count
00-08
P.37
Speed display
0: Display output frequency(not mechanical speed)
0.0
1~50000
1~9999
00-09
P.259
Multi-function display unit
selection
X0: Speed display unit is 1
1
X1: Speed display unit is 0.1
0X: Power accumulation rate unit is 1
1X: Power accumulation rate unit is 0.1
2X:
Power accumulation rate unit is 0.01
00-11
P.72
Carrier frequency
Frame A/B/C: 1~15kHz
5 kHz
Frame D/E: 1~9 kHz
4 kHz
Frame F/G: 1~9 kHz
2 kHz
Frame H: 1~3 kHz
2 kHz
00-12
P.31
Soft-PWM carrier function
selection
0: Off
0
1: When 00-11(P.72)< 5, Soft-PWM is on (only
apply to V/F control )