Appendix 1 Parameter table
APPENDIX 363
Group
Parameter
Number
Name
Setting Range
Default
Page
02-20
P.17
Terminal 4-5 signal range
selection
0: Signal sampling range from 4~20mA.
0
1: Signal sampling range from 0~10V.
2: Signal sampling range from 0~5V.
02-21
P.39
Terminal 4-5 maximum
operation frequency
50Hz system: 1.00~650.00Hz
50.00Hz
60Hz system: 1.00~650.00Hz
60.00Hz
02-22
P.528
Terminal 4-5 filter time
0~2000ms
30ms
02-23
P.505
Terminal 4-5 current/ voltage
signal
bias rate
-100.0%~100.0%
0.0%
02-24
P.184
Terminal 4-5 disconnect
selection
0: Off
0
1: Inverter decelerates to 0Hz, muti-function digital
output terminal set off alarm
2: Inverter stops immediately, and keypad displays
“AEr” alarm
3: Inverter runs continuously according to the
frequency command before disconnection. Digital
output terminal will set off alarm.
02-25
P.198
Terminal 4-5 minimum input
current/ voltage
0~20.00mA
4.00mA
02-26
P.199
Terminal 4-5 maximum input
current/ voltage
0~20.00mA
20.00mA
02-27
P.196
Percentage corresponds to
terminal 4-5 minimum input
current/ voltage
-100.0%~100.0%
0.0%
-400.0%~400.0%(02-00(P.500)= 2/14/15/16/17)
02-28
P.197
Percentage corresponds to
terminal 4-5 maximum input
current/ voltage
-100.0%~100.0%
100.0%
-400.0%~400.0%(02-00(P.500)= 2/14/15/16/17)
02-29
P.531
Terminal 3-5 signal range
selection
0: Signal sampling range from 4~20mA
1
1: Signal sampling range from 0~10V
2: Signal sampling range from 0~5V
02-30
P.508
Terminal 3-5 maximum
operation frequency
50Hz system: 1.00~650.00Hz
50.00Hz
60Hz system: 1.00~650.00Hz
60.00Hz
02-31
P.527
Terminal 3-5 filter time
0~2000ms
30ms
02-32
P.507
Terminal 3-5 current/voltage
signal
bias rate
-100.0%~100.0%
0.0%
02-33
P.545
Terminal 3-5 disconnect
selection
0: Off.
0
1: Inverter decelerates to 0Hz, muti-function digital
output terminal set off alarm
2: Inverter stops immediately, and keypad displays
“AEr” alarm
3: Inverter runs continuously according to the
frequency reference before disconnection. Digital
output terminal will set off alarm.