Appendix 1 Parameter table
APPENDIX 334
Parameter
Number
Group
Name
Setting Range
Default
Page
P.247
10-29
Switch to commercial supply MC
switch-over interlock time
0.1~100.0s
1.0s
P.248
10-30
Switch to commercial supply
waiting time
0.1~100.0s
0.5s
P.249
10-31
From inverter to commercial power
supply switch-over frequency
0~60.00Hz
99999
99999: Off.
P.250
10-32
Automatic switch-over frequency
range
0~10.00Hz: After switching from inverter
operation to commercial power supply operation,
after inverter start command (STF/STR) is OFF,
switch to inverter operation.
99999
99999: After switching from inverter operation to
commercial power supply operation, after
inverter start command (STF/STR) is OFF,
switch to inverter operation, and slow down to
stop.
P.251
08-43 PID pressure range (Bar) setting
1.0~100.0
100.0
P.252
08-44 PID unit selection
0: %
0
1: bar
2: --
3: kgs
4: kg
5: psi
6: Pa
7: kPa
8: MPa
9: C
P.253
08-45
Disconnection detection time
feedback
0.0~600.0s
0.0s
P.254
08-46
Disconnection processing method
feedback
0: AEr alarm, inverter free stop
0
1: Slow down and stop, call AEr alarm
2: AEr alerts and continues running
P.255
01-36
S curve time at the beginning of
acceleration
0~25.00s/0~250.0s
0.20s
P.256
01-37
S curve time at the end of
acceleration
0~25.00s/0~250.0s
99999
99999: Off
P.257
01-38
S curve time at the beginning of
deceleration
0~25.00s/0~250.0s
99999
99999: Off
P.258
01-39
S curve time at the end of
deceleration
0~25.00s/0~250.0s
99999
99999: Off
P.259
00-09
Multi-function display unit
selection
X0: Speed display unit is 1
1
X1: Speed display unit is 0.1
0X: Power accumulation rate unit is 1
1X: Power accumulation rate unit is 0.1
2X:
Power accumulation rate unit is 0.01