Appendix 1 Parameter table
APPENDIX 387
Group
Parameter
Number
Name
Setting Range
Default
Page
10-46
P.268
Regeneration avoid action voltage
level
220V : 155~400V
380V
440V : 310~800V
760V
10-47
P.269
Regeneration avoid function DC bus
voltage detection sensitivity at
deceleration
0: Prevent regeneration avoidance from failing
according to bus voltage change rate
0
1~5: Set the sensitivity to detect the bus
voltage change rate. Larger number, higher
sensitivity.
10-48
P.270
Regeneration avoid frequency
compensation value
0~10.00Hz: Set the limit value of regenerative
avoid frequency compensation.
6.00Hz
99999: Off.
10-49
P.271
Regeneration avoid
voltage gain coefficient
0~400.0%/0~40.0%
100.0%
10-50
P.272
Regeneration avoid frequency gain
coefficient
0~400.0%/0~40.0%
100.0%
10-51
P.264
Over excitation deceleration
0: Off.
0
1: Over excitation deceleration is valid.
10-52
P.265
Over excitation current level
0~200.0%
150.0%
10-53
P.266
Over excitation gain
1.00~1.40
1.10
10-54
P.362
Short-circuit brake time when PM
motor start
0~60.0s
0.0s
10-55
P.780
PLC function selection
0: Off
0
269
1: PLC RUN signal from digital input terminal
function 60 or 10-56 (P.781)。
2: PLC RUN signal from digital input terminal
function 60
10-56
P.781
PLC run
0: Off
0
269
1: PLC RUN
10-57
P.782
PLC program erase function
0: Off
0
269
1: Erase the PLC program, after erase success
parameter value is 0.
10-58
P.783
PLC choose register to monitor
0~326
0
269
10-59
P.784
PLC register monitoring value
Read only
Read
only
269
11-00
P.320
Speed control proportional
coefficient 1
0~2000.0
100
11-01
P.321
Speed control integral time 1
0~20.00 s
0.30s
11-02
P.322
PI coefficient switch-over frequency
1
0~11-05(P.325)Hz
5.00Hz
11-03
P.323
Speed control proportional
coefficient 2
0~2000.0
100
11-04
P.324
Speed control integral time 2
0~20.00s
0.30s
11-05
P.325
PI coefficient switch-over frequency
2
11-02(P.322)~650.00Hz
10.00
11-06
P.326
Current control proportional
coefficient
0~20
0