Analog input and output parameter group 02
PARAMETER DESCRIPTION 129
voltage
10V
60Hz
0Hz
60Hz
Reverse
rotation area
Forward
rotation area
5V
-10V
-5V
02-09
(
P.38)=60Hz Max operation frequency
02-12(P.192)=0V, 02-13(P.193)=10V The
minimum/maximum input positive voltage of terminal 2-5
02-14(P.194)=-100%,02-15( P.195)=100% The setting
corresponding to the minimum/maximum positive voltage
of terminal 2-5
02-18(P.510)=-100%, 02-19(P.511)=100% The setting
corresponding to the minimum/maximum negative voltage
of terminal 2-5
02-16(P.512)=0V,02-17( P.513)=10V The
minimum/maximum input negative voltage of terminal 2-5
02-11(P.139) = 0% The bias rate of 2-5 voltage signal
Frequency
(Hz)
Example 10: This example is the application with bias voltage. The bias voltage is set by 02-11(P.139). When
02-11(P.139)=0%, there is no bias voltage; When 02-11(P.139)>0%, there is the positive bias voltage;
When 02-11(P.139)<0%, there is the negative voltage.
02-09
(
P.38)=60Hz Max operation frequency
02-12(P.192
)
=0V, 02-13
(
P.193
)
=10V The minimum/maximum
input positive voltage of terminal 2-5
02-14
(
P.194
)
=0%, 02-15
(
P.195
)
=100% The setting corresponding
to the minimum/maximum positive voltage of terminal 2-5
02-18(P.510)=0%, 02-19(P.511)=100% The setting corresponding to the
minimum/maximum negative voltage of terminal 2-5
02-16(P.512
)
=0V, 02-17
(
P.513
)
=10V The minimum/maximum
input negative voltage of terminal 2-5
02-11
(
P.139
)
= 50% The bias rate of 2-5 voltage signal
60Hz
10V
-10V
5V
-5V
0
30Hz
voltage
Frequency
(Hz)
Note: 1.
Above is only an example of 02-00(P.500) = 1. and the same applies when 02-00(P.500) is another non-zero
value. For details, refer to the description of 02-00(P.500).
2. If use 02-08(P.73) to select 2-5 terminal voltage signal sampling range, it will affect the relevant value in
section 5.3.5 parameter group of the 2-5 terminal input signal..