Analog input and output parameter group 02
PARAMETER DESCRIPTION 116
Group
Parameter
Number
Name
Setting Range
Default
Page
02-04
P.54
Terminal AM1 output
function
9: Output torque, use two times motor rated torque
as 100%.(Valid only when 00-21 (P.300) or 00-22
(P.370) is set to 3~6)
0
10: Output power, use two times motor rated power
as 100%.
11: High-speed pulse input, use 100KHz as 100%.
12: Motor speed, use 02-51 (P.55) as 100%
13:PLC analog output, for details please refer to
SA3 built-in PLC manual
02-05
P.537
Terminal AM2 output
function
6: Fixed output, voltage or current output level can
be set by 02-53(P.539).
0
0~5, 7~13: Same as 02-04(P.54).
02-06
P.185
Proportional linkage gain
0~100%
0%
02-07
P.240
Auxiliary frequency
0: Off
0
1: Output frequency = basic fre auxiliary
frequency (given by terminal 2-5)
2: Output frequency = basic fre auxiliary
frequency (given by terminal 4-5)
3: Output frequency = basic frequency - auxiliary
frequency (given by terminal 2-5)
4: Output frequency = basic frequency - auxiliary
frequency (given by 4-5 terminal)
5: Output frequency = proportional linkage signal
(given by terminal 2-5)
6: Output frequency = proportional linkage signal
(given by terminal 4-5)
7: Output frequency = proportional linkage signal
(given by terminal 3-5)
8: Output frequency = basic fre auxiliary
frequency (given by terminal 3-5)
9: Output frequency = basic frequency - auxiliary
frequency (given by terminal 3-5)
02-08
P.73
Terminal 2-5 signal range
selection
0: Signal sampling range from 0 ~5V.
1
1: Signal sampling range
from 0 ~10V.
2: Signal sampling range from 0 ~ -5V.
3: Signal sampling range from 0 ~ -10V.
4: Signal sampling range from -5~+5V.
5: Signal sampling range from -10~+10V.
02-09
P.38
Terminal 2-5 maximum
running frequency
50Hz system: 1.00~650.00Hz
50.00Hz
60Hz system: 1.00~650.00Hz
60.00Hz
02-10
P.60
Terminal 2-5 filter time
0~2000ms
30ms
02-11
P.139
Terminal 2-5 voltage signal
bias rate
-100.0%~100.0%
0.0%
02-12
P.192
Terminal 2-5 minimum
input positive voltage
0~10.00V
0.00V
02-13
P.193
Terminal 2-5 maximum
input positive voltage
0~10.00V
10.00V
02-14
P.194
Percentage corresponds to
terminal 2-5 minimum
positive voltage
-100.0%~100.0%
0.0%
-400.0%~400.0%(02-00(P.500)= 2/14/15/16/17)