Ways to measure voltage, current , power on main circuit
INSPECTION AND MAINTENANCE 316
6.2.6 Measurement of insulation resistance
Inverter insulation resistance
1.
Before measuring the inverter insulation resistance, first dismount the
wiring of all the main-circuit terminals and control board. Then do the wiring
as shown in the right picture.
2.
The measurement is only suitable for the main circuit. It is prohibited to
use a high-resistance meter for measuring terminals on the control board.
3.
The value of the insulation resistance shall be greater than 5MΩ.
Note: Please use a 500 VDC meter.
Motor insulation resistance
1.
Before the measurement, please dismount the motor, and wire
as shown in the diagram on the right.
2.
The value of the insulation resistance shall be greater than 5MΩ.
Note: Please use a suitable meter.
6.2.7 Hi-pot test
Do not conduct a hi-pot test. Deterioration may occur on the internal semiconductor components of the inverter.