Application parameter group 10
PARAMETER DESCRIPTION 269
Built-in PLC
Select any terminal from digital input terminals M0, M1, M2, STF, STR, M3, M4, M5, RES, HDI or terminals on
expansion board EB308R or EB362R, and set its corresponding function to PLC_ON_STOP (parameter setting
value is 60). This sets PLC’s RUN signal. Please refer to 5.4 for details of input terminals and expanded digital
input terminals.
PLC running status when 10-55(P. 780) =1
P.781
External PLC_ON_STOP signal
PLC state
0
0
STOP
1
0
RUN
0
1
RUN
1
1
RUN
PLC running status when 10-55(P. 780) =2
External PLC_ON_STOP signal
PLC state
0
STOP
1
RUN
10-58(P.783) selects PLC component for monitoring, and the value of10-59(P. 784) is the status of current
monitoring PLC components, as shown in the following table.
10-58(P.783)
10-59(P.784)
10-58(P.783)
10-59(P.784)
1
X0~X17 (The name is in octal)
20
T0~T7( bit)
2
X20~X25 (The name is in octal)
21
C0~C7(bit)
3
Y0~Y17 (The name is in octal)
22
M8000~M8015
4
Y20~Y23 (The name is in octal)
23
M8016~M8031
5
M0~M15
24
M8032~M8047
6
M16~M31
25
M8048~M8063
7
M32~M47
26
M8064~M8079
8
M48~M63
27~52
Reserved
9
M64~M79
53~60
T0~T7 Set value (word)
10
M80~M95
61~68
Reserved
11
M96~M111
69~76
C0~C7 Set value
12
M112~M127
77~84
Reserved
13
M128~M143
85~92
T0~T7 Set value (word)
14
M144~M159
93~100
Reserved
15
M160~M175
101~108
C0~C7 Set value (word)
16
M176~M191
109~116
Reserved
17
M192~M207
117~164
D0~D47
18
M208~M223
165~326
D8000~D8161
19
M224~M239
Setting