Application parameter group 10
PARAMETER DESCRIPTION 254
5.11.5 Remote control function
If operation box is located away from control cabinet, without analog signal, variable speed can still be realized
through digital input.
Parameter
Name
Default Setting Range
Content
10-11
P.61
Remote control
function
0
0
Off
X1
Remote control function, frequency save in memory
X2
Remote control function, frequency won’t save
X3
Remote control function, frequency won’t save, clear
frequency setting every time STF/STR “turn off”.
X4
With remote function and frequency can be stored. The
interval between 2 frequency memories should be over 5s.
1X
Target frequency range is 01-01(P.2)~01-00(P.1) and which
is derived from the frequency setting during RH, RM
operation.
Remote function
In external mode, combined mode 1,combined mode 5, use digital input to change output frequency.
Acceleration
(
RH
)
Deceleration
(
RM
)
Clear
(
RL
)
Forward
rotation
(
STF
)
ON
ON
ON
ON
ON
ON
ON
ON
ON
Power supply
Output
frequency
(
Hz
)
0
Time
*
* When 10-11(P.61)=0X,
it’s external target frequency
(other than multi-speed) or PU running
target frequency, which is called master speed frequency.* When 10-11(P.61)=1X, it is 01-01(P.2),
which is lower frequency limit.
10-11(P.61)=X1/X2/X4
10-11(P.61)=X3
10-11(P.61)=X2/X3
10-11(P.61)=X1/X4
Remote function setting
1.
10-11(P.61) decides remote function and ways to save frequency.
Set 10-11(P.61)=X1~X4(remote setting function is valid), terminal RM, RH , RL will be accelerate (RH),
decelerate (RM) and clear (RH).See following figure:
Inverter
Forward rotation
Acceleration
Deceleration
Clear
STF
RH
RL
RM
SD
10
2
5
2.
If 10-11(P.61)=1~4, the target frequency of inverter=( frequency setting during RH,RM ope external
frequency( other than multi-speed)/ PU running frequency)
If 10-11(P.61)=11~14, the target frequency of inverter=frequency setting during RH, RM operation.
Setting