Multi-speed parameter group 04
PARAMETER DESCRIPTION 168
Frequency
M0
ON
ON
ON
ON
ON
ON
ON
ON
……
04-19
P.131
04-20
P.132
04-21
P.133
04-22
P.134
04-23
P.135
04-19
P.131
04-20
P.132
0
Time
Note: 1. This program can run 8 speeds
at most, which can be set by 04-19(P.131)~04-26(P.138).
2.
Settings for parameters 04-15(P.100)~04-18(P.123)and 04-27(P.101)~04-42(P.118) are only for the
programmed operation mode not manual cycle mode.
For the acceleration and deceleration time of manual
cycle mode, please refer to 01-06(P.7), 01-07(P.8), 01-22(P.44) and 01-23(P.45).
3. If any segment is set to zero, inverter will return to standby state when run to this segment.
This means that
when this mode is selected, 04-19(P.131) cannot be 0.
As shown in the above diagram, if 04-24(P.136) is 0,
regardless of the values of 04-25(P.137) and 04-26(P.138), inverter will stop running when the switch is
pressed for the sixth time.
4. Manual cycle function rotation direction is single direction, which has nothing to do with the operation direction
parameter 04-16(P.121) of each speed in the programmed operation mode, and has nothing to do with STF
and STR signals.
5. For 04-35(P.111)~04-42 (P.118), please refer to acceleration and deceleration time increments parameter
01-08(P.21).