PG feedback parameter group 09
PARAMETER DESCRIPTION 244
5.11 Application parameter group 10
Group
Parameter
Number
Name
Setting Range
Default
Page
10-00
P.10
DC brake operating
frequency
0~120.00Hz
3.00Hz
10-01
P.11
DC brake operating time
0~60.0s
0.5s
10-02
P.12
DC brake operating voltage
0~30.0%: 7.5K/11KF and below
4.0%
0~30.0%: 11K/15KF~55K/75KF
2.0%
0~30.0%: 75K/90KF and above
1.0%
10-03
P.151
Zero-speed control function
selection
0: Off.
0
1: Zero speed control is performed at zero speed.
2: In close-loop vector mode do zero-servo.
10-04
P.152
Voltage at zero-speed
control
0~30.0%: 7.5K/11KF and below
4.0%
0~30.0%: From 11K/15KF to 55K/75KF
2.0%
0~30.0%: 75K/90KF and above
1.0%
10-05
P.242
DC brake before inverter
start
0: Off
0
1: Before starting operate DC brake first.
10-06
P.243
DC brake time before
inverter start
0~60.0s
0.5s
10-07
P.244
DC brake voltage before
inverter start
0~30.0%: 7.5K/11KF and below
4.0%
0~30.0%: 11K/15KF~55K/75KF
2.0%
0~30.0%: 75K/90KF and above.
1.0%
10-08
P.150
Restart mode selection
XX0: No frequency search.
0
XX1: Direct frequency search
XX2: Decrease voltage mode
X0X: Power on once.
X1X: Start each time.
X2X: Only instantaneous stop and restart
0XX: No rotation direction detection.
1XX: Rotation direction detection.
2XX:00-15(P.78)=0, rotation direction detection;
00-15(P.78)=1/2, no rotation direction detection.
10-09
P.57
Restart idling time
0~30.0s
99999
99999: Off.
10-10
P.58
Restart rising time
0~60.0s: 7.5K/11KF and below.
5.0s
0~60.0s: From 11K/15KF~55K/75KF
10.0s
0~60.0s: 75K/90KF and above.
20.0s