Basic operation steps for different modes
BASIC OPERATION 75
Step
Description
3
•Inverter starting is activated by communication (including “Reset”). At this point, indicating lamp
FWD
or
REV
will flash, indicating that the motor is running.
Note: 1. For detailed operation procedures for the monitoring mode, please refer to Section 4.2.3.
2.
When the motor is running, the frequency can also be set. You can change the target frequency in the
memory to change the motor speed.
4
•When communication sends in stop command, the motor will decelerate until it comes to a full stop.
• Indicator in
FWD
or
REV
will not turn off until the inverter stops outputting.
4.3.9 Basic operation steps for combined mode 5(00-16(P.79)=8)
Step
Description
1
•In Combined Mode 5, indicator in
PU
will flash.
Note: 1. For detailed operating procedures for monitor mode, please refer to section 4.2.
2
• The default priority is from high to low.
• When the external JOG is ON, the target frequency is determined by the value of 01-13(P.15), and the
acceleration/deceleration time is determined by the value of 01-14(P.16).
• When M0, M1, M2, REX multi-speed are ON, you can perform the target speed setting by multi-speed
combination setting, please refer to section 5.5.1 Multi-speed 16.
• Performing target frequency setting by PU301 operation panel.
3
•Inverter starting is triggered by external STF or STR terminals.
Note: 1. For detailed operation procedures for the monitoring mode, please refer to section 4.2.3.
2.
When the motor is running, the frequency can also be set. You can change the target frequency in the
memory to change the motor speed.
4
•When digital input terminals output stop signal, the motor will decelerate until it comes to a full stop.
• Indicator in
FWD
or
REV
will not turn off until the inverter stops outputting.
4.3.10 Basic operation steps for second operation mode(00-16(P.79)=99999)
In second operation mode, target frequency is determined by 00-17(P.97), and the run command is determined by
00-18(P.109), please refer to Section 5.1.9 Operation mode selection for related description and Section
4.3.1~4.3.5 for related operation method.