Appendix 1 Parameter table
APPENDIX 331
Parameter
Number
Group
Name
Setting Range
Default
Page
P.170
08-00
PID function selection
4X: Terminal HDI input as target source
0
X1: Terminal 2-5 input as feedback source
X2: Terminal 4-5 input as feedback source
X3: Terminal 3-5 input as feedback source
P.171
08-01
PID feedback control
method
0: Negative feedback control.
0
1: Positive feedback control.
P.172
08-04
Proportional gain
0.1%~1000.0%
20.0%
P.173
08-05
Integral time
0~60.00s
1.00s
P.174
08-06
Differential time
0~10000ms
0ms
P.175
08-07
Abnormal deviation
0~200.0%
0.0%
P.176
08-08
Abnormal duration time
0~600.0s
30.0s
P.177
08-09
Abnormal processing
mode
0: Stop freely
0
1: Slow down to stop
2: Alarm and continue operation
P.178
08-10
Sleep detection deviation 0~100.0%
0.0%
P.179
08-11
Sleep detection duration
time
0~255.0s
1.0s
P.180
08-12
Wake-up level
0~200.0%
90.0%
P.181
08-13
Stop level
0~120.00Hz
40.00Hz
P.182
08-14
Upper integral limit
0~200.0%
100.0%
P.183
08-15
Deceleration step length
when stable
0~10.00Hz
0.50Hz
P.184
02-24
Terminal 4-5 disconnect
selection
0: Off
0
1: Inverter decelerates to 0Hz, muti-function digital
output terminal set off alarm
2: Inverter stops immediately, and keypad displays
“AEr” alarm
3: Inverter runs continuously according to the
frequency reference before disconnection. Digital
output terminal will set off alarm.
P.185
02-06
Proportional linkage gain
0~100%
0%
P.186
00-23
Motor types selection
0: Normal Duty (ND), on fan and pump duty type.
1
1: Heavy Duty (HD), apply to other duties.
P.187
02-59
FM calibration coefficient 0~9998
450
P.188
00-01
Firmware version
Read only
Read
only
P.189
00-24
50Hz/60Hz switch
selection
0: Frequency related parameter default value is
60Hz.
0
1: Frequency related parameter default value is
50Hz.
1
P.190
02-47
Terminal AM1 output bias 0~5000
80
P.191
02-46
Terminal AM1 output gain 0~5000
3210
P.192
02-12
Terminal 2-5 minimum
input positive voltage
0~10.00V
0.00V