background image

Automation Components, Inc.

2305 Pleasant View Road  |  Middleton, WI 53562

Phone:

 1-888-967-5224  |  

Website:

 workaci.com

Page 1

Version: 7.0

I0000598

FIGURE 1: 

DIMENSIONS

INTERFACE SERIES

Installation & Operation Instructions

AUD

Phone:

 1-888-967-5224

Website:

 workaci.com

GENERAL INFORMATION

The AUD converts a floating point signal into a 
linear analog output. There are two inputs on the 
AUD, one to increase the analog output and one to 
decrease the analog output. The output of the AUD 
is stable when the inputs are both off. A contact 
closure or voltage signal to either input will cause 
the output of the AUD to begin to ramp either up or 
down depending on which input was activated. 
The output stops ramping once the up or down 
input is deactivated, and will remain at that value 
until another up or down signal is received. If both 
inputs are “ON,” the output will reset to the lowest 
value of the selected range.

 The output and the AUD 

is in the form of an analog, steady state voltage or 
current. This signal can be scaled to fit the needs of the 
application by selecting one of several preset ranges 
by dip switch or by adjusting the offset and the gain of 
the output with two potentiometers.

MOUNTING INSTRUCTIONS

Circuit board may be mounted in any position. If circuit board slides out of snap track, a non-conductive 
“stop” may be required. Use only fingers to remove board from snap track. Slide out of snap track or push 
against side of snap track and lift that side of the circuit board to remove. 

Do not flex board or use tools.

WIRING INSTRUCTIONS

PRECAUTIONS
•     Remove power before wiring. Never connect or disconnect wiring with power applied.
•    When using a shielded cable, ground the shield only at the controller end. Grounding both 
ends can cause a ground loop. 
•   It is recommended you use an isolated UL-listed class 2 transformer when powering the unit 
with 24 VAC. Failure to wire the devices with the correct polarity when sharing transformers may 
result in damage to any device powered by the shared transformer.
•    If the 24 VDC or 24VAC power is shared with devices that have coils such as relays, solenoids, or 
other inductors,  each coil must have an MOV, DC/AC Transorb, Transient Voltage Suppressor (ACI 
Part: 142583), or diode placed across the coil or inductor. The cathode, or banded side of the DC 
Transorb or diode, connects to the positive side of the power supply. Without these snubbers, 
coils produce very large voltage spikes when de-energizing that can cause malfunction or 
destruction of electronic circuits.
•    All wiring must comply with all local and National Electric Codes.

3.75” (95.25mm)

2.20”

(55.88mm)

2.18”

(55.37mm)

3.88” (98.55mm)

0.70” 

(17.78mm)

Note: 

If the end device has an earth ground(SCR, VFD), the 

ground/common must be isolated. This can be achieved by using an 
isolated transformer. R16 resistor will be extremely hot to the touch if 
there is a ground loop.

Note:

  If J1 jumpers are set to the NRM position, but the controller is 

outputting a Triac signal for UP pulse, the UP LED will be turned on 
and the DOWN LED will be slightly dim.  This would be an indication 
that the jumpers need to be set for TRIAC.  

Summary of Contents for INTERFACE AUD

Page 1: ...rd may be mounted in any position If circuit board slides out of snap track a non conductive stop may be required Use only fingers to remove board from snap track Slide out of snap track or push against side of snap track and lift that side of the circuit board to remove Do not flex board or use tools WIRING INSTRUCTIONS PRECAUTIONS Remove power before wiring Never connect or disconnect wiring wit...

Page 2: ...OWN Output Pulsed relay contacts not Isolated PWR UP DWN 24V SIG E2 Wiring diagram for TEC controller mfg by Siemens Building Technologies Inc Landis Division PWR UP DWN 24V SIG E4 Triac 24 VAC from Controller Can share same power supply as TEC Controller N O N O C C NRM TRC U D J1 Triac Jumper Positon E5 24 VAC DC Power Supply Note If the end device has an earth ground SCR VFD the ground common m...

Page 3: ...ds to version ordered See Table 1 2 Select either current or voltage output with the two switches shown in Figure B on p 4 NEVER have both switches on or off at the same time while powered or chip failure may occur 3 Select offset of 1 volt 4 mA or adjustable offset by switch 6 as shown in Figure C With the adjustable offset setting you can adjust the OFFSET trim pot as desired For offset higher t...

Page 4: ... Turn power OFF set DIP switch 6 for adjustable offset see Figure 3 connect multimeter to the output and turn the power on Place Man Auto jumper in the Manual position Turn the Manual Override potentiometer counter clockwise until it stops It is a 3 4 turn pot Offset Pot turns counter clockwise to Decrease and clockwise to Increase Turn the Offset potentiometer until the desired minimum output is ...

Page 5: ...he hookup to the actuator place Jumper J2 in MAN manual position and turn the manual potentiometer Be sure to return Jumper J2 to AUTO position after testing TROUBLE SHOOTING AND TESTING 1 Apply 24 VAC or 24 VDC to PWR terminal confirm power LED is on and measure voltage to confirm proper voltage 2 Check the DIP settings Depressing the switch closest to the MAN AUTO pot selects the ON position You...

Page 6: ...stated above If no contact ACI Tech Support at 888 967 5224 If yes current output is functioning properly 4 Testing the input To manually test the input Apply 24 VAC or 24 VDC to the PWR terminal Connect your meter to the SIG and PWR terminal Set meter to match output DIP switch settings Place MAN AUTO jumper to AUTO Connect a jumper wire from UP to the PWR Connect a jumper wire to the PWR only Yo...

Page 7: ...uracy 0 to 16 mA 4 to 20 mA 0 to 20 mA with adjustable offset and span 0 to 750Ω maximum If the load is lowered to 700Ω the DC supply can be 24 VDC 10 and maintain stated accuracy Absolute 2 of span for adjustable ranges 5 for preset Absolute 3 of span for adjustable ranges 5 for preset 256 steps all ranges 24 VDC 10 48 mA maximum 90 Pluggable Screw Terminal Blocks 16 1 31 mm2 to 26 AWG 0 129 mm2 ...

Page 8: ...nc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Page 8 Automation Components Inc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Version 7 0 I0000598 ...

Reviews: