Basic parameter group 01
PARAMETER DESCRIPTION 113
5.2.12 S curve time
It is used to set S curve acceleration/deceleration time.
Parameter
Name
Default Setting Range
Content
01-36
P.255
S curve time at the
beginning of
acceleration
0.20s
0~25.00s/
0~250.0s
01-08 = 0/
01-08 = 1
01-37
P.256
S curve time at the end
of acceleration
99999
0~25.00s/
0~250.0s
01-08 = 0/
01-08 = 1
99999
Not selected.
01-38
P.257
S curve time at the
beginning of
deceleration
99999
0~25.00s/
0~250.0s
01-08 = 0/
01-08 = 1
99999
Not selected.
01-39
P.258
S curve time at the end
of deceleration
99999
0~25.00s/
0~250.0s
01-08 = 0/
01-08 = 1
99999
Not selected.
S pattern time
When 01-05(
P.29
) = 3 “S curve acceleration /deceleration curve 3”.
Output
frequency
Time
Starting
signal
ON
OFF
01-36(
P.255)
01-37(
P.256)
01-38(
P.257)
01-39(
P.258)
1)
Parameters 01-36(P.255), 01-37(P.256), 01-38(P.257) and 01-39(P.258) are used to start inverter gradually
without impact. And adjust the value to vary degrees of S shape acceleration / deceleration curve. When the
S shape acceleration / deceleration curve is started, the inverter will accelerate/decelerate with different
speed according to the primary acceleration/deceleration time.
2)
When S shape acceleration/deceleration curve 3 is selected, the acceleration/ deceleration time will be longer,
as follows.
3)
When selected acceleration time (01-06(P.7) or 01-22(P.44))≥01-36(P.255) and 01-37(P.256), the actual
acceleration time is as follows:
Actual acceleration time = the selected acceleration time + (01-36(P.255) + 01-37(P.256)) / 2
4)
When selected deceleration time (01-07(P.8) or 01-23(P.45))≥01-38(P.257) and 01-39(P.258), the actual
deceleration time is as follows:
Actual deceleration time = the selected deceleration time + (01-38(P.257) + 01-39(P.258))/ 2